If an overspeed is detected, the unit trips. As the speed exceeds the currently
displayed peak speed, the peak speed is updated and stored in non-volatile
memory. The operator interface is still active. That is, all parameters can be
displayed, and tunable parameters can be changed.
Peak speed is not stored in non-volatile memory if an overspeed condition has
not occurred.

To reset a unit's peak speed, place the key switch in the PROGRAM position,
then press the RESET key. The message "RESET PEAK? ADJ = YES ADJ
= NO" appears. Press the ADJ key to reset the peak speed. After pressing
either the ADJ or the ADJ keys, the unit resumes normal operation. If
neither key is pressed within 10 seconds, a "no" response is assumed and the
prompt disappears. Return the key switch to the MONITOR position.
Up to two Remote RTN modules may be installed into each MicroNet Plus 8/14 expansion chassis (only
one RTN for 6/12 slot expansion chassis). When initialized by the main chassis CPU, the Remote RTN
modules will acquire either a SYSCON or STANDBY status. The Remote RTN module that becomes
SYSCON will control the expansion chassis where it is located. It will synchronize with the STANDBY
Remote RTN module and perform any redundancy functions as necessary. Input and output data from all
I/O modules will be managed appropriately and made available to the GAP Application running in the
main-chassis CPUs.