The Modbus® TCP/IP to IEC 61850 gateway enables communication between
the Intelligent Electronic Devices (IEDs) on an IEC 61850 network and
Programmable Logic Controllers (PLCs) or Programmable Automation
Controllers (PACs) on a Modbus TCP/IP network.
The configuration utility software provided with the gateway uses IED
configuration files to import complex IEC 61850 data structures. The utility
creates Variable files and Function Block files for import into Unity Pro projects
for Quantum or M340 processors.

IEC 61850 is the international standard that defines the hardware and
communication requirements for all devices within substation automation. The
standardized naming conventions imposed by the IEC 61850 standard
improves interoperability between systems provided by diverse manufactures or
created by multiple system integrators.
Features
Configuration Utility Integrates
Tightly with Unity Pro
Application-specific Variable and Function Block files are automatically generated.
Users are not required to develop communication logic or tag structures in their PLC or PAC
projects.
Configuration Archive and
Diagnostics
The gateway configuration file can be stored on an optional removable 1GB industrial SD
card. This allows for rapid disaster recovery by moving the SD card from a failed gateway to
a replacement gateway.
Extensive diagnostics for the gateway and for both Modbus TCP/IP and IEC-61850 networks
are available via the configuration utility.
Import Configured IED files
All IED data attributes are available for convenient mapping to Modbus registers.
Modbus TCP/IP Client/Server
support
Enables multiple Modbus TCP/IP devices or SCADA devices to interface with IEC-61850
devices simultaneously.
Configuration
ProSoft 61850 Configuration Manager software, provided with the gateway, is used to develop and manage gateway
configuration files, as well as to view communication and network diagnostics.
Import CID and SCD files
Drag and drop IEC 61850 Data Attributes for Modbus mapping
PLC or PAC Tag names are automatically created
Print mapped tag list
Tag file export (.CSV)
Export .XSY (Variable) and .XFM (Function Block) files for use with Unity Pro
Specifications - Modbus TCP/IP
The Modbus TCP/IP driver allows multiple independent, concurrent Ethernet
connections. The connections may be Clients, servers, or a combination of both Clients
and servers.
Modbus TCP/IP Client
Actively reads data from and writes data to Modbus TCP/IP devices using MBAP
messages on Service Port 502 or Encapsulated Modbus RTU messages on other
Service Ports.
Supports up to 10 Client connections (max. 2000 commands) to multiple servers.
Modbus Command optimization - Multiple tags can be combined into one Write
command with up to 120 words.
Modbus TCP/IP Server
Accepts incoming connections on Service Port 502 from Clients using Modbus
TCP/IP MBAP messages and on Service Port 2000 (or other Service Ports) from
Clients using Encapsulated Modbus messages.
Supports up to 20 independent, concurrent server connections for any combination
of Service Port 502 MBAP messages and Encapsulated Modbus RTU messages
on other Service Points.