Features
User-friendly display and operator controls
Backlit operating buttons. Text display suitable for
night-time operation
Surface mounting
Designed to meet EN 54 and LPCB requirements, and
conforms to CE standards
Complies with environmental conditions of IEC-721
3-3 class 3k5

Application/Description
From the Fire Brigade Panel BU-210 it is possible to mute
the panel’s internal buzzer, silence sounders/bells etc.
and reset the system. Only alarms are shown in the
display.
The panel is menu operated on a 8-line display, with 40
characters per line.
The BU-210 communicates with the Fire Alarm Control
Panel BS-200. Information Panels BV-210. Repeater
Panels BS-211. other Fire Brigade Panels BU-210 and
Mimic Drivers BUR-200 on an RS-485 panel bus.
Indicators
8 x 40 character alphanumeric display
Alarm, More Alarms, Pre-Alarm, Remote Call, Fault,
Disabled Function, Delayed Activation, Power
Internal buzzer
Operator Controls
More Events, Mute panel, Silence, Reset
Backlit buttons and text
Fireman’s key
Capacity
A maximum of 8 additional panels can be freely
mixed and connected to the Fire Alarm Control Panel
via the RS-485 panel bus, including Repeater Panels
BS-211. Information Panels BV-210. Fire Brigade
Panels BU-210 and mimic Drivers BUR-200
Addressing the Panel
The rotary switch on the rear side of the panel (on the
left side of the connector J13 and J14) is used to address
the panel (1-9)