The MVI56 Limitorque Valve Actuator Master Communication Module allows
ControlLogix compatible processors to interface easily with Limitorque Valve
Actuators and other Limitorque protocol compatible devices.
The MVI56-LTQ module acts as an input/output module between the Limitorque
valve network and the ControlLogix processor. The data transfer from the
ControlLogix processor is asynchronous from the actions on the network. The
1500-word register space in the module transfers the valve information from the
module to the processor. Ladder logic is responsible for control of the valves.
Data transferred from the processor to the module instructs the module to
execute commands to valves on the Limitorque network.

Functional Specifications
Support for the storage and transfer of up to 150 valves to the ControlLogix
processor’s controller tags
Emulates Limitorque’s Port A/B polling scheme using both ports on the module
Supports the following valves
o MX/DDC Modbus
o UEC-3-DDC Modbus
o DDC-100M I/O module
o DDC-100M field unit
o Valvcon IVO (unit in multi-drop mode only)
Software configuration
o Baud rate: 1200 to 115200
o Message response timeout
o Number of active slaves
o Last state on communication failure for valve data
o Network polling scheme
o Active slave table (bit mapped)
o Use of CTS module line option
Support command
o Continuously polled
o Read registers 40008 to 40013. optional 40055 or 40006/40007
o Commands: open, stop, close, initiate network ESD, terminate network ESD,
engage contactors 1 to 6. disengage contactors 1 to 6. position valve (0 to 100%)
Data returned to the processor for each valve
o Valve position
o Status register
o Fault register
o Digital outputs
o Digital inputs registers 1 and 2
o Communication error code
o Communication poll counter
o Special polled registers