The PROFIBUS PA gateway allows the user to interface PROFIBUS
PA DPV0/DPV1 to either EtherNet/IP™ or Modbus® devices.
When configured as a Master, the PA Link can exchange up to 2
kilobytes of PROFIBUS PA device and status data.
The PA Link has two Ethernet ports for a Linear or Ring (Device Level
Ring – DLR) Ethernet topology. The Ethernet ports can also be
configured for port mirroring, allowing for better fault analysis.

The PA Link can synchronize to an NTP Server allowing for automatic
time synchronization. It also supports an onboard non-volatile event log
for improved fault finding. The PA Link has a built-in Power Conditioner
which can supply up to 420 mA. The power conditioner is protected
against a configurable overcurrent limit. The module also has a
configurable built-in Fieldbus terminator.
The PA Link provides a range of statistics and tools to provide a
detailed diagnostic overview of each PA Link, which speeds-up fault
finding. The Slate Configuration Utility allows the user to perform a
PROFIBUS PA packet capture of the running Fieldbus which can be
used to analyze the bus behavior and packets received. The PA Link
also provides global and device specific statistics.
Features
• Direct link from PROFIBUS PA to EtherNet/IP or Modbus TCP/IP
• Exchange up to 2 kilobytes of PROFIBUS PA device and status data
• Support for up to 32 PROFIBUS PA slave devices
• Embedded 2 port Ethernet switch – DLR capable
• Built-in Isolated PA Power Conditioner – Max. 420 mA (Temperature limited)
• Configurable bus Current Protection (Trip)
• Built-in configurable Bus Terminator
• Supports PROFIBUS PA Master Redundancy (Active / Standby)
• FDT Asset Management - DTM Available
Configuration
• The Slate Configuration Utility software is used for configuration and
troubleshooting of the module. The stand-alone configuration utility allows
users to define the setup and configuration of the PROFIBUS PA module,
connections with controllers and devices.