Brief Introduction
The AutroSafe Self Verify™ Integrated Fire and Gas detection system
described in key words is as follows:
Both the Fire Detectors as well as the Gas Detectors can be
connected to the same panel or system.
All detectors are interactive addressable devices with intelligent
communication. Non-addressable detectors can be connected via
a 4-20mA interface.

Field devices have a built-in calibrated self-test to verify and
confirm their ability to perform correctly. This can be considered as
supplemental to – and can be used instead of – manual testing and
inspection routines. Refer to Chapter 4.4.
Flame and Gas Detectors can be connected to the AutroSafe
Panel by using a 2-wire loop structure (PowerLoop). The
PowerLoop provides both power to, as well as interactive
communication with the detectors. Studies have shown that the
Fire & Gas Detection Control System’s cable requirement can be
reduced with 30-60% by utilizing this concept as opposed to
conventional systems.
AutroSafe SelfVerify™ IFG is a modular and distributed system
providing maximum flexibility. The AutroNet communication
facilitates the possibility to link cause and effect across panels
within the same AutroNet. In other words, any detector connected
to any panel can activate any output associated to any panel. Each
panel can have up to 12 custom AutroSafe I/O modules. Within the
limitations of the system, the system designer can freely select the
type and number of modules to be used.
There are a number of versatile communication options available:
Physical: Ethernet, RS-232. RS-422. RS-485. Al_Com loop,
AutroFieldBus, PowerLoop and either hardwired or fibre-optic
based AutroNet (Ethernet).
Protocols: Modbus RTU Slave or Master, Modbus TCP/IP
Slave or Master, ESPA 4.4.4. and AutroCom (Autronica’s
proprietary protocol).
The figure below shows an example of a typical AutroSafe Integrated
Fire & Gas system:
Fully integrated PowerLoop detectors are connected to the two
wire PowerLoop, no additional interfaces are required.
Any 4-20mA devices can be connected to the system’s PowerLoop
by means of the BN-342 4-20mA interface. No additional power
supply is required, the PowerLoop will supply both the BN-342
module as well as the detector attached to it.
Advanced Open Path Gas Detectors connected to the BN-342 4
20 mA interface provides the highest level of detection
performance. Including, but not limited to false alarm immunity,
logging and trending of analogue detector readings.
The smoke- and heat detectors on the Al_Com loop employ the
DYFI+ technology, a dynamic filtering system which virtually
eliminates false alarms and provides the earliest possible warning
of a potential fire. A single pair of wires that provides both power to
– as well as interactive communication with – the detectors,
connects detectors, manual call points and interfaces. The Al_Com
loop also features the SelfVerify function, testing the detectors to
the calibrated set point every 24hours.
Automatic addressing of detectors – No switch settings required.
For a detailed general description of the AutroSafe SelfVerify™
Integrated Fire and Gas System, please refer to Chapter 4.4.