Features
• SelfVerify function for automatic testing of detectors
• Automatic addressing of detectors
• AutroFieldBus
• Accommodates up to a maximum of 12 modules, of
which maximum 6 can be Loop Driver Modules
• User-friendly display and operator controls
• Backlit operational buttons. Text display suitable for
full darkness operation
• Surface mounting on wall
• Rack mounting in standard 19’’ cabinets
• Conforms to applicable EU directives and regulations
• SIL2 capable according to IEC 61508
• Approved according to CEN Standards EN 54-2.
EN 54-4 and EN 54-13. FM regulations (Factory
Mutual) and maritime regulations (IMO/SOLAS and USCG)

Description / Application
BS-420 is a complete fire alarm control panel with full
operation capabilities. The panel serves as an operating
panel for one or several defined operation zones. All
alarm handling and system features can be controlled
and monitored from the panel.
The panel can accommodate up to a maximum of 12
modules. The system offers Loop Driver Modules for
detection loops and several types of I/O modules (see
Optional Modules below).
There can be a maximum of 6 Loop Driver Modules in
each panel. All modules are easily plugged onto each
other on a standard mounting rail inside the unit.
The panel provides connections for 2 Ethernet ports and
2 USB host ports.
The panel is menu operated on a 16-line display, with 40
characters per line. A printer is available as an option.
The panel communicates with other system units on the
Ethernet-based local area network, AutroNet.
Optional Modules
• Loop Driver Module (BSD-310/311) for connection of
detection loops
• Output Module (BSB-310) with 4 monitored outputs
• Output Module (BSJ-310) with 8 open collector non
monitored outputs
• Input Module (BSE-310) with 4 monitored inputs
• Input Module (BSE-320) with 8 non-monitored inputs
(galvanically isolated)
Indicators
• 16 x 40-character alphanumeric display
• Fire, More Events, Fire Brig. Signaled, Fault, Function
Disabled, Testing, System Fault, Power, Function
Delayed, Alarms Fault, Fire Brig. Fault, Alarms
Disabled, Fire Brig. Disabled, Detector Inhibit,
Extinguishing Activated, Extinguishing Isolated, Local
Mode, Dual Safety Stdby, MultiS SmokeDis.
• Internal buzzer
Operator Controls
• More Events, Mute Panel, Silence Alarms, Reset
System, Menu, Close Window
• Keyboard with alphanumeric characters and scroll
function
• Separate buttons for menu operation
• Backlit buttons and text
Capacity
• 64 system units (panels) on the local area network;
AutroNet
• 15000 loop units per system
• 12 modules per fire alarm control panel, of which 6
can be Loop Driver Modules
• 512 detectors and manual call points can be
connected to each Fire Alarm Control Panel (EN 54)
• 31 AutroFieldBus units connected to AutroFieldBus
• 127 loop units connected to one detection loop
• 40 socket/loop sounders connected to one detection
loop
• 15 loop units connected to one Powerloop
wechat/whatsapp:
+86-181-44100-983
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved