The power supplies can only be installed into slots PS1 (power supply #1) and PS2 (power supply #2). If
redundant power supplies are not needed, blanking plates must be installed in the slots not being used.
Branch circuit fuses, circuit breakers, and wiring must meet appropriate codes and authorities having
jurisdiction for the specific country (CE, UL, etc.). See Table 4-3 for maximum recommended fuse or
breaker ratings. Do not connect more than one main power supply to any one fuse or circuit breaker. Use
only the wire sizes specified in Table 4-3. which meet local code requirements. Time delay fuses or circuit
breakers must be used to prevent nuisance trips.

Power requirements depend on the number and type of modules supplied for each system. For a system
with a single I/O chassis, size the input power source according to the rating of the MicroNet Plus power
supply to which the source is connected. Do not size the supply mains for the sum of the MicroNet Plus
power supply ratings when redundant supplies are used. MicroNet Plus supplies are redundant when
installed in the same chassis. Redundant supplies share the load between them equally, but each must
provide for full load in the event that one of the units is disabled. Table 4-3 gives the maximum overload
protection for supply mains connected to any single or redundant pair of MicroNet Plus main power
supplies. It is not recommended that both MicroNet Plus main power supplies of a redundant pair be
connected to a single source, since failure of that source would disable the system.
Triconex Pass-Through Module, Any I/O Type, NIS D6001S
Triconex Pass-Through Module, Any I/O Type, NIS D6004S
Triconex IOA FEED-THRU/EX (ETP IOA Feed-Through Module) 2906598
Triconex Safety Relay, 2xNC 2702971
Triconex Analog Input with HART D5014S
Triconex Analog Input with HART D6017SK
Triconex Analog Output with HART Intrinsically Safe D5020S
Triconex Digital Input Intrinsically Safe D5031S
Triconex Supervised Digital Input Intrinsically Safe D5038SB
Triconex Digital Input Not Intrinsically Safe D5093S
Triconex Supervised Digital Output Intrinsically Safe D5049S
Triconex Digital Output Not Intrinsically Safe D5090S
Triconex Digital Output Not Intrinsically Safe D5091S
Triconex Supervised Digital Output Not Intrinsically Safe D5096S
Triconex Supervised Digital Output Not Intrinsically Safe D5097S
Triconex Analog Input Intrinsically Safe D5072S-099