Emerson Controlinc Network Masters are the master of Emerson Controlinc valve
actuator networks with Modbus RTU protocol. The system provides network management,
data concentration and protocol conversion, off-loading the host system of these tasks.
This enhances overall system performance and minimizes software development and
system configuration tasks by the system integrator. The Network Master serves as the
master of a master/slave network. It manages the network by keeping an orderly cycle of data
transfers to and from the slave devices (valve actuators). It handles error detection, alarming,
and network recovery. The Network Master serves as a data concentrator for the host by
providing a common database for all slave devices. The host is required to communicate
with only one slave device (network master) for all data transfers to and from the field.

Data can be transferred between the network master and host in large blocks at a much
higher communications rate than would be possible if the host communicated with each
slave device (valve actuator) on the field network. The Network Master acquires data from
the valve actuators by polling or scanning each device in a sequence of slave address from
a table called a scan list. Polling is a process of the Network Master sending to each slave
address, a command to return its status information, including alarms, discrete and analog
inputs and outputs. When control commands (valve open, stop, close, position set point, etc.)
are generated by a host system up-line of the Network Master, it then sends the appropriate
commands over the network to the addressed slave device. A more detailed functional
description of operation is provided in the Theory of Operation section of this manual.
System Configuration
The field network is wired in a ring configuration from Port A around a loop to Port B of the
network master. Beginning at Port A, the network is wired to Port A of the first actuator and
then from Port B of the first actuator to Port A of the second actuator and so on until the
network returns from Port B of the last actuator to Port B of the network master. Networks
may have parallel wired (bus wired) actuators between series wired actuators. Always wire
parallel actuators to Port A and remove termination and bias. Do not connect more than 15
actuators in parallel between any two series connected actuators. Networks are polarized with
(+) and (-) symbols on all drawings. Proper operation requires that polarity be observed at all
connections. Connect the field networks to the Port A and B connectors on the NIM in the
network master as shown in Figure 9. The networks must be connected to Port A and Port B
of the valve actuators as shown in the wiring diagram of the XTE3000/ICON3000 IOM.