• For For Foundation™ fieldbus networks in hazardous areas
• Integrated redundant fieldbus power for FBM228
Foundation™ fieldbus modules
• 8-segment redundancy
• High-density, compact design
• Fully isolated
• Low power dissipation
• No components on carrier
• Built-in "smart" termination
• Continuous physical layer diagnostic option

The F810 fieldbus power system is designed to provide redundant
Foundation™ fieldbus power for Foxboro I/A Series control systems
using FBM228 modules. Eight fieldbus segments are supported. The
system comprises a baseplate which accommodates two redundant
pairs of Foxboro FBM228 modules and two Eaton F801 or F802 power
modules operating in redundant configuration. Failure alarms, galvanic
isolation, power conditioning and segment termination are incorporated
into each F80x module. In applications requiring simplex power, a single
F80x module may be used.
For extreme reliability, the module baseplate has no components and
only provides interconnections between FBM228 modules, the power
modules and external connections.
Each F80x module has indicator LEDs to show both its status and
that of the eight segments under power. In normal operation, each
green 'Segment' LED is lit, showing that the segment is powered. If a
segment is shorted, this LED is extinguished, and the red 'Alarm' LED
is lit. In the alarm condition, a normally closed, galvanically-isolated relay
contact goes to an open condition. Connections to the alarm relay are
made via screw terminals on the F810 baseplate. If multiple F810 units
are used, a common alarm circuit can be achieved by 'daisy-chaining'
the alarm circuits.
The F80x module provides galvanic isolation between the
24V DC input power and the fieldbus segments, as required by
the IEC61158-2 fieldbus standard and the Fieldbus Foundation™
FF-831 validation test for power conditioners. There is also galvanic
isolation between the fieldbus segments, thereby preventing multiple
segment failures from ground faults on more than one segment. Each
segment has its own fieldbus power conditioner and current limitation.
Termination of the fieldbus segment is automatically maintained when
single or redundant F80x modules are fitted.
An F809F-Plus diagnostic module may optionally be installed on the
carrier, to automatically collect and distribute diagnostic information on
each of the eight fieldbus segments. Measured parameters may be
viewed in the Foxboro control system by either assigning the F809F
Plus as a fieldbus device to segment 1 or 8 of the powered segments,
or by means of a separate fieldbus segment. Connections for the
separate segment are provided on the baseplate. For more information
see the F809F-Plus product specification.
Redundant 24V DC (nom.) input power can be connected to the F810
baseplate using Foxboro I/A standard AMP connectors. F80x power
modules and the F809F-Plus fieldbus diagnostic module can either
be powered from the same source or, alternatively, for installations in
which standard Foxboro power supplies are unable to provide sufficient
current capacity, an external 24V DC supply may be connected.
Field wiring connections are available with either pluggable screw
terminals (F810-PS) or pluggable spring clamp terminals (F810-PC).