The MVR-V211 busbar protection relay offers voltage and frequency
protection and can operate as a synch-check relay (ASNI 25) for up
to three circuit breakers. With its powerful logics programming and
expandable communication and I/O it is ideal for compley load
shedding and ATS (Automatic Transfer Switch) applications.

4x Voltage input (1.00…480.00V (RMS)
3x Digital input
5x Output relay (4NO, 1CO)
1x IRF output (1CO)
2 x Remote com port (1 x RJ45 Ethernet and 1 x RS-485)
- IEC 61850 Ed1. Modbus TCP/RTU, IEC 60870-5-104/103/101. DNP
3.0. SPA protocols
- 5 extension slots for additional hardware options
- Event recorder (up to 15 000 events)
- Disturbance recorder (up to 100 disturbance records)
- Synchro-Check (ANSI 25) for up to three circuit breakers
- Anti Islanding Protection
Available Extension Cards:
- 8x digital inputs (programmable threshold voltage)
- 5x output relays
- Arc-Flash Protection - 4x sensor channels, 2x HSO1. 1x BI *)
- 8x RTD input
- 2x RJ45 100Mb Ethernet & IRIG-B *)
- 2x ST 100Mb Ethernet & IRIG-B *)
- 4x mA outputs - 1 x mA input
- 2x LC 100MB Ethernet (HSR, PRP redundant protocols)
- 2x RJ45 100MB Ethernet (HSR, PRP redundant protocols) *)
- RS-232 - Serial Fiber
Features
Protection Functions:
• Breaker failure protection (ANSI 50BF)
• Frequency protection stages (ANSI 81O/U)
• Fuse failure (ANSI 60)
• Overvoltage protection INST, DT or IDMT (ANSI 59)
• Positive/negative sequence under-/over-voltage protection INST, DT
or IDMT (ANSI 27P/47/59P)
• Programmable stage (ANSI 99)
• Rate of Change of Frequency ROCOF (ANSI 81R)
• Residual voltage protection INST, DT or IDMT (ANSI 59N)
• Synchrocheck (ANSI 25)
• Under-voltage protection INST, DT or IDMT (ANSI 27)
• Vector jump/surge (ANSI 78)