The ELX3152-0090 analog input terminal allows the direct connection of
intrinsically safe field devices located in hazardous areas classified zone
0/20 or 1/21. It supplies measuring transducers located in the field and
transmits their analog measuring signals electrically isolated to the
automation device. The measuring range can be switched between 0...20
mA and 4...20 mA by software.

With a technical measuring range of ±107% of the nominal range, the
terminal also supports commissioning with sensor values in the limit range
and evaluation according to NAMUR NE43. The error LEDs indicate an
overload condition and wire breakage. The error LEDs indicate an overload
condition and wire breakage.
With the aid of the TwinSAFE SC technology (TwinSAFE Single Channel) it
is possible to make use of standard signals for safety tasks in any network
or fieldbus. To do this, EtherCAT I/Os from the areas of analog input,
position measurement or communication (4… 20 mA, incremental encoder,
IO-Link, etc.) are extended by the TwinSAFE SC function.
The properties typical for the signals and the standard functions of the I/O
components are retained. TwinSAFE SC I/Os differ optically from standard
I/Os by a yellow stripe on the front of the housing.
The TwinSAFE SC technology enables communication via a TwinSAFE protocol.
These connections can be distinguished from the usual secure communication
via Safety over EtherCAT.
The data from the TwinSAFE SC components is fed via a TwinSAFE protocol
to the TwinSAFE Logic, where it can be used in the context of safety-relevant
applications. Detailed examples confirmed/calculated by the TÜV SÜD for the
correct application of the TwinSAFE SC components and the respective
normative classifications can be found in the TwinSAFE application manual.