OVERVIEW
The F892 redundant fieldbus power supply is designed to provide redundant power
for eight (8) Foundation fieldbusTM H1 segments. Pluggable connectors are provided
on the F892-CA module carrier for connection to the eight segments. Fixed screw
terminals are used for the 8 Host segment connections. Power for the eight fieldbus
segments is provided by two F801 or F802 Power Modules mounted to the carrier
and operating in a redundant configuration. Failure alarms, galvanic isolation, power
conditioning and segment termination are incorporated into each Power Module. A
single F801 or F802 module may be used where redundancy is not required.

DESCRIPTION
For maximum reliability, the module carrier contains no components and only provides
interconnections between the power modules and the external connections. The
carrier circuit board is supported in a rigid metal frame that protects it from mechanical
damage. Secure DIN-rail mounting is provided by integrated retaining screws. The
Power Module provides galvanic isolation between the 24V DC input power and the
fieldbus segments, as required by the IEC61158-2 fieldbus standard and the Fieldbus
FoundationTM FF-831 validation test for fieldbus power supplies. There is also galvanic
isolation between the fieldbus segments, thereby preventing cross-talk between
segments in the event of ground faults in the field wiring. Each segment has its own
current limitation and passive fieldbus power conditioner. Termination of the fieldbus
segment is automatically maintained when single or redundant Power Modules are
fitted. The F892-CA carrier is equipped with connectors that will accept an F809F
diagnostic module. The module continuously monitors the performance of each of the
eight fieldbus segments, providing information on the network health.
Each Power Module has indicator LEDs to show both its status and that of the eight
segments under power. In normal operation, each green ‘Segment’ LED is lit, showing
that the segment is powered. If a segment is shorted, or its voltage is below the rated
output, its LED is extinguished, and the red ‘Alarm’ LED is lit. Redundant 24V DC (nom.)
input power is connected to the F892-CA carrier using two-part pluggable connectors.
Field wiring connections are available with either pluggable screw terminals (F892-PS)
or pluggable spring clamp terminals (F892-PC).
The figure below shows two sets of 8 connectors for connection to the Host. Early
versions of the F892 only included one set of connectors (unit date code 0711 and
earlier) and thus did not support redundant Host connection.
COMPONENTS AND ACCESSORIES
F801 8 Segment Power Module: 21 .5V, 350mA
F802 8 Segment Power Module: 28V, 500mA
F809F 8 Segment Fieldbus Diagnostic Module
F892-CA-P* Carrier
F892-P* F892-CA-P* and two F801 modules
F892-2-P* F892-CA-P* and two F802 modules
F892-P*-NR F892-CA-P* and one F801 module
F892-2-P*-NR F892-CA-P* and one F802 module
F800-BLK Blanking Module included with –NR systems
* =
S – Pluggable Screw Terminal Connectors
C – Pluggable Spring Clamp Connectors