The ELM3002-0325 EtherCAT Terminal in the basic series is designed
for low-voltage measurement in high-voltage systems (AC or DC),
especially current measurement via shunt or single-cell measurement.
It has an adjustable measuring range of ±60 mV to ±5 V per channel
and electrical isolation between the channels.

The measuring range is selected in the CoE, as are the other setting
options such as the filter parameters. Regardless of the signal
configuration, all ELM modules have the same technological properties,
and the ELM3002-0325 with oversampling offers a maximum sampling
rate of 50.000 samples per second and channel.
The terminal is equipped with 4 mm laboratory sockets.
The individual Beckhoff factory calibration certificate can be downloaded
via Beckhoff Service.
here for each device. Recalibration (ZS9001) is possible
Extensive documentation is available from Beckhoff sales, support or
measurement@beckhoff.com.
This ELM3xxx series measurement terminal enables efficient implementation
of complex system-integrated data acquisition systems (DAQ) that place
high demands on measurement accuracy and time synchronization.
The EL3783 EtherCAT Terminal is a power monitoring I/O terminal
used for state monitoring of a 3-phase AC voltage system.
For each phase, voltage up to 400/690 Vrms and current up to 1
Arms/5 Arms are sampled as instantaneous values with a resolution
of 16 bits. The six channels are measured simultaneously based on
the EtherCAT oversampling principle with a temporal resolution of
up to 50 µs and then passed on to the control system.
With the processing power available there and in combination with
the TwinCAT Function TF3650. true RMS or power calculations as
well as complex user-specific algorithms can be calculated via the
voltage and current characteristics. Through the oversampling
principle, the terminal is able to measure at significantly shorter
intervals than the cycle time of the control system.
AC and DC parameters must be connected and measured with a
common reference potential.
Through the feature “ExtendedRange”, the user has the full technical
measuring range available at up to 130% of the specified nominal
measuring range. The EL3783 supports distributed clocks and can
therefore measure synchronously with other EtherCAT devices.
In combination with EL6688 it can be synchronized via IEEE 1588 to
external clocks. The terminal can also be operated without distributed
clocks.