The M‑0127A AC Current Relay is primarily designed as a recommended
addition to the Circulating Current or Delta VAr1 Paralleling configurations
used with LTC Transformers. Its purpose is to monitor the current in the
circulating loop between transformers, and interrupt Motor Power to its
monitored transformer, should the circulating current exceed a
predetermined value. The M‑0127A range permits the maximum circulating
current to be set from 5% to 50% of the rated full load current.
Other relays used for this purpose have an impedance exceeding 5.000 Ω
which may cause the main CT to saturate, making the entire circulating
current scheme operate poorly. The low impedance of the M‑0127A relay
avoids this problem.

The output should be connected in series with the common lead of the
automatic control circuit of the motor starter relay. When used with the
Beckwith Electric M‑0067E control, the M‑0127A output contacts will be
in series with the lead that would otherwise have gone directly to terminal
TB1‑8 of the M‑0067E. Polarity of the M‑0127A input and output can be
ignored.
M‑0170A Application
The M‑0170A AC Current Relay is intended to be used in the load current
circuit to prevent the tapchanger from changing taps on excessive load
current. Its range permits the current setting from 100% to 200% of the
rated full load current. The relay is connected in the same manner as the
M‑0127A.
Additional Applications
The M‑0127A and M‑0170A can be used wherever an adjustable, low burden
AC relay is required. They have virtually no time delay, a very small hysteresis
and a normally closed output for use on AC only. The relay output draws
approximately 6 mA of in‑phase current through a 120 Vac load when open.
These factors must be considered for the user’s specific application.
By adding external series resistors, the relays may be used for voltage sensing.
For example, with a 10 K series resistor, the M‑0127A is adjustable from 100 to
140 Vac, using 10 to 14 mA current setting range.
Use of a 10 K, 10 W wire‑wound resistor is suggested.
Transformer relay protection systems are crucial for safeguarding transformers
within electrical distribution networks, designed to detect and respond to
abnormal conditions like overloads and short circuits. By monitoring transformer
performance and electrical parameters, these systems quickly identify potential
issues and initiate corrective actions, such as disconnecting power or adjusting
settings to maintain stability. Equipped with advanced technologies such as
differential, overcurrent, and thermal protection, these systems are tailored for
various applications, from industrial to utility-scale projects.
Essential for protecting assets and ensuring operational continuity, transformer
relay protection enhances the reliability and efficiency of power distribution
networks.
The M-7679 R-PAC offers protection, automation, and control capabilities
for recloser, switch, sectionalizer, and advanced distribution automation
applications. It has over 30 protection elements for optimal protection
of power distribution systems. It is compatible with three-phase ganged
and independent phase capable switching devices such as reclosers,
switches, sectionalizers, and breakers. It has up to six standard or low
energy analog (LEA) voltage inputs. The M-7679 R-PAC has a recloser
settings wizard that assists in creating files for most common settings
for recloser applications. The comprehensive I/O matrix provides visual
confirmation of enabled functions and selected outputs, improving security.
Additionally, it includes one of a kind Sensitive Ground Indicator feature to
detect high-impedance faults on the distribution line.
The M‑2067B is an adapter panel which, when combined with the M‑2001
Series Digital Tapchanger Control, provides convenient direct replacement
for Westinghouse SVC and SVR controls and Beckwith Electric M‑0067
series controls. The M‑2067B can also be used, with the M‑2001 Series
Tapchanger Control, as a general purpose LTC transformer control.
The M‑2067B permits changing of the M‑2001 control without adapter
panel removal or rewiring.

Applications
• Connects easily to the M‑2001Series Digital Tapchanger Control using
four mounting screws and 24‑pin connector
• Provides mounting adaptable to several different configurations
• Provides built‑in CT shorting protection when the M‑2001 Series Digital
Tapchanger Control is removed
The M‑2053 is an adapter panel which permits M‑2001 Series Digital
Tapchanger Controls to be surface‑mounted while providing access points
for wire terminations.
Testing Specifications
High Voltage: All input and output terminals will withstand 1500 Vac rms to
chassis or instrument ground for one minute with a leakage current not to
exceed 25 mA, for all terminals to ground. Input and output circuits are
electrically isolated from each other, from other circuits and from ground.
Surge Withstand Capability: All input and output circuits are protected against
system transients. Units pass all requirements of ANSI/IEEE C.37.90.1-1989
defining surge withstand capability.
Radiated Electromagnetic Withstand Capability: All units are protected against
electromagnetic radiated interference from portable communications transceivers
as outlined in ANSI/IEEE C37.90.2-1987 defining radiated electromagnetic
withstand capability.
• M-2948 Tap Position Sensor directly mechanically replaces the Selsyn-Type Tap
Position Sensor.
• Directly interfaces with a 4 to 20 mA output to the M-2025D Current Loop Interface
which provides the tap position to the M-2001 Series Tapchanger Control.
• Rotation – 0 to 210°, 297°, 306°, 315°, 325°, 330°, 340° and 350° configurations
• Degrees per Tap – 9° or 10°
• Neutrals – 1, 2, 3, 5 or 6
• Rotation Direction – Tap Position Sensors are available with either a positive
or negative rotation. With positive rotation, the shaft of the M-2948 rotates
clockwise while raising taps. With negative rotation, the shaft of the
M-2948 rotates counter-clockwise while raising taps.
The M‑2069 Adapter Panel, when combined with the M‑2001C or M-2001D
Digital Tapchanger Control, offers convenient, direct replacement of
Westinghouse SVC or SVR controls and Beckwith Electric M‑0067E controls
or M-2067B adapter panels.
The M‑2069-M-2001D combination can also be used as a general purpose
LTC transformer control.
Beckwith M-0193 Syncrocloser Unit |
Beckwith Electric generator protection system M-3420 STOCK G365 |
Beckwith Electric M-4272 Integrated Synchronizing Systems Motor Bus Transfer |
Beckwith M-0115A Parallel Balancing Module Made in USA. |
Beckwith M-3425 Integrated Generator Protection |
BECKWITH ELECTRIC M-3425A Generator Prothection |
Beckwith Electric M-3425A Integrated Generator Protection Relay |
BECKWITH ELECTRIC M-3425A INTEGRATED GENERATOR PROTECTION RELAY M-3425A |
Beckwith Electric M-3520 Intertie Protection Relay |
BECKWITH M-0193B SYNCROCLOSER UNIT (RR4) |
BECKWITH ELECTRIC M3420 GENERATOR PROTECTION RELAY |
BECKWITH / M-0245B HIGH SPEED SYNC-CHECK |
Beckwith Electric M-3420 Integrated Generator Protection Module |
Beckwith Electric M-3311A 8 Output D-0179 60-140 VAC Transformer Protection. |
Beckwith P-1939 Generator Protection Relay Annunciator Panel B-0898 Rev A-2 |
| User name | Member Level | Quantity | Specification | Purchase Date |
|---|
wechat/whatsapp:
+86-181-44100-983
Email: kongjiangauto@163.com