Control Network: The DeltaV Control Network providescommunication between
the nodes in the DeltaV network.Refer to the Installing Your DeltaV Digital
Automation Systemmanual for complete information on the Control Network.
Local Bus: The Local Bus provides communication between DeltaV controllers
and SLS 1508 Logic Solvers and between DeltaV controllers and SISnet Repeaters.
Local Peer Bus (SISNet): SLS 1508 Logic Solvers communicatewith other SLS 1508
Logic Solvers and with local SISNet Repeaters through the carriers over
a 2 channel local peer bus.

The same message is broadcasted over both channels. The localpeer bus must
be terminated at both ends. The local peer bus is terminated at the left
end through the 2-wide power/controller carrier and at the right end
through a terminated 1-wide carrier.
System Compatibility
M-series I/O carriers are not physically compatible with
S-series controller carriers, except when used with the
DeltaV SIS Adapter.
The M-series controllers cannot detect the difference between
an 8-wide and a 4-wide carrier. If a 4-wide carrier is used,
the four I/O slots after the slots on the carrier will be lost to
an M-series controller. If either a 4-wide or 8 wide carrier is
connected after a 4-wide carrier, the first slot number will
be 5 numbers higher than the last slot on the 4-wide carrier.
For example, if a controller has a 4-wide carrier followed by
an 8-wide carrier, the slots on the 4-wide carrier will be
1. 2. 3. and 4. and the slots on the 8-wide carrier will be
slots 9. 10. 11. 12. 13. 14. 15. 16. The PK Controller does
not have this behavior because it can distinguish between
a 4-wide and an 8-wide carrier. However, there is still a limit
of 8 total carriers (4-wides and/or 8-wides) on any controller.