While the SLS 1508 Logic Solver is rated suitable for use in SIL 3 applications
in simplex mode, it is installed in redundant pairs for increased process availability.
Redundant SLS 1508 Logic Solvers run in parallel at all times.Both read the inputs
from the I/O terminals, both execute the logic and both drive the outputs at the I/O terminals.
There is no concept of primary and backup or master and slave,which is unlike any other SIS.
The only difference between the two is that one communicates with both the engineering
and operator workstations and the dedicated safety network (SISNet);
this is the one with the Active light on the bezel.The other (Standby) is
communicating only on the SISNet.In the event that a failure is detected in
one of the SLS 1508 Logic Solvers, it automatically goes to a failed state.

In this condition, all its output channels are de-energized;
this has no impact on the other SLS 1508 Logic Solver or the physical
outputs because the other SLS 1508 Logic Solver continuesto read inputs
execute logic and drive outputs. The transition from redundant to simplex
mode is therefore completely bumpless.
With DeltaV SIS process safety system, events are automatically generated as
function blocks are executed within a module scan. Events are time stamped
with a resolution of <1 ms,and they are recorded in the sequence that they occur in the
Event Chronicle. When using standard function blocks such as input blocks,
|voter blocks, and cause and effect blocks, a standard set of events are
automatically generated without special configuration or programing required.
For example,I/O failures, trip limits, first outs, and other similar events are automatically
time stamped by function blocks and recorded in the Event Chronicle.
When a process variable exceeds the trip limit, DeltaV SIS records the event along
with the analog value and the trip condition.
The health and status of both SLS 1508 Logic Solvers and their channels are
available in the diagnostics explorer.
When one of a redundant pair of SLS 1508 Logic Solversis removed online there
is no disturbance to the process.
When the missing SLS 1508 Logic Solver is replaced with another SLS 1508 Logic Solver,
the new SLS 1508 Logic Solver completes its power-up self-tests before the
active Logic Solver cross-loads the current database.
In safe areas, failed SLS 1508 Logic Solvers can be replaced under power.
In hazardous areas,appropriate installation procedures must be followed.
Automatic proof testing can be selected on a redundant pairof SLS 1508 Logic Solvers.
The desired proof-test interval is set in the configuration and the SLS 1508 Logic Solvers perform
the proof test automatically. A warning is given to the operator before
the automatic proof test is started.

MOLEX BRAD HARRISON WOODHEAD 302001A01F060 47402-90 CORD SET
AM&E Wheatley Hills Driver, 3 & 5 Fairway Woods Headcovers Set Black White
Woodhead 15050-50TT 50' Tri-Outet GFCI Cord-Set 15A 120V
PROFINET Card 5136-PBMSLV SST Woodhead
SST / WOODHEAD 5136-SD-PCI ALLEN BRADLEY MOLEX DH+ REMOTE I/O INTERFACE CARD
Shock Absorber Set Rear Woodhead Brand Fits Jaguar XJR XJ8 VDP X308 MNC3540AA
Shock Absorber Set Gas Front Woodhead Brand Fits Jaguar XJR XJ8 & Vanden Plas
Woodhead Fits Jaguar XJ6 XJ12 & Vanden Plas 09906x2
Woodhead PC104 Board SST DNP-104-LC V1.0.2 490-1725 REV 1.0.0
SST/Woodhead 050803040014 490-1082 Board
Woodhead 302101A04M050, 5M, 12-Pole, 18 AWG & 22 AWG, Single Ended Cordset, 1pc
Woodhead/Molex 31659-30 1301790077 spring assembly
WOODHEAD 804000A34M100A 1200652176 18-4C 10M CORD SET , S2
MOLEX ARC30MHDAB04, WOODHEAD ARCARREST PLUG KIT, 1122191018
WOODHEAD SST SST-IBS-SLC INTERBUS SCANNER
| User name | Member Level | Quantity | Specification | Purchase Date |
|---|
wechat/whatsapp:
+86-181-44100-983
Email: kongjiangauto@163.com
Copyright © 2009 - 2026 Cld , All Rights Reserved K-JIANG All rights reserved