An MPU loss-of-signal occurs when an MPU frequency of less than 100 Hz is
measured and the previously measured speed was greater than 120 Hz. The
alarm relay de-energizes, and the MPU FAIL LED turns on and remains on until
a reset or until power is cycled. If the TRIP ON MPU FAILURE option is "yes", a
trip occurs. If the previously measured speed is less than 120 Hz, it is assumed
that a normal rolldown has occurred. The MPU FAIL LED does not turn on, the
alarm relay does not de-energize, and no trip occurs.
After a normal rolldown, each ProTech unit monitors the MPU. If the MPU
frequency exceeds 110 Hz, the unit trips and annunciates the cause as NO RESET.

When the short circuit has been removed, the supply will resume normal operation (Note that if the 24 V or 5 V outputs
are shorted, these power converters will be latched OFF and can only be cleared by removing the shorted
condition and removing the input power for 1 minute (or until the front panel LEDs extinguish). If no short
circuit is found, reset the supply by removing input power for one minute. If the power supply is still not
functioning after input power has been restored, verify that the supply is properly seated to the
motherboard connector. If the supply is properly seated but is not working, then replace the supply.
Simplex Power Supply Checks
The following is a troubleshooting guide for checking areas which may present difficulties. If these checks
are made prior to contacting Woodward for technical assistance, system problems can be more quickly
and accurately assessed.
• Is the input power within the range of the control’s power supply input?
• Is the input power free of switching noise or transient spikes?
• Is the power circuit dedicated to the governor only?
• Are the control’s supplies indicating that they are OK?
• Are the control’s supplies outputting the correct voltage?
• Is the RTN / CPU Low Vcc LED ON?
Woodward Discrete Input - 16 Channel 8200-1104
Woodward Discrete Output - 16 Channel 8200-1105
Woodward Termination Resistor Kit 8923-1889
Woodward Dataforth I/O Thermocouple - K-Type 1784-1028
Woodward Dataforth I/O RTD - 100 Ohm 1784-655
Woodward Dataforth I/O 4-20 mA Input 1784-659
Woodward Table A. NetCon Analog Cables 12 feet, Black 5416-349
Woodward Table A. NetCon Analog Cables 14 feet, Black 5416-350
Woodward Table A. NetCon Analog Cables 16 feet, Black 5416-351
Woodward Dataforth I/O 0-5 VDC Input 1784-657
Woodward Network Switches Ethernet - 8 Port, RJ45 Connectors 1711-1350
| User name | Member Level | Quantity | Specification | Purchase Date |
|---|
wechat/whatsapp:
+86-181-44100-983
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved