Product Description
The safety-related F3 AIO 8/4 01 remote I/O is a compact system located in a metal
enclosure with 8 analog inputs and 4 analog outputs.
The remote I/O is available in three model variants for SILworX and three model variants
for ELOP II Factory, see Chapter 3.3. All variants are described in this manual.
The remote I/O serves as extension of the I/O level of HIMax and HIMatrix controllers, and
is connected to them via safeethernet. The remote I/O itself is not able to run a user
program.

The HIMatrix remote I/Os are not multi-master capable.
The remote I/O is suitable for mounting in Ex-zone 2. see Chapter 4.1.3.
The device has been certified by the TÜV for safety-related applications up to SIL 3 (IEC
61508. IEC 61511 and IEC 62061), Cat. 4 (EN 954-1) and PL e (EN ISO 13849-1). Further
safety standards, application standards and test standards are specified in the certificate
available on the HIMA website.
Safety Function
The remote I/O is equipped with safety-related analog inputs. The input values on the
inputs are safely transmitted to the connected controller via safeethernet. The outputs are
safely assigned their values by the connected controller via safeethernet.
Safety-Related Analog Inputs
The remote I/O is equipped with 8 analog inputs with transmitter supplies for the unipolar
measurement of voltages, referenced to L-.
The remote I/O is intended to measure the voltage on the inputs. To measure the current
on the inputs, connect a resistor of up to 500 Ω in parallel to each input.
Only shielded cables with a length of a maximum of 300 m must be connected to the
analog inputs. Each analog input must be connected to a twisted pair of wires. The
shielding must be connected to the remote I/O and the sensor housing and earthed of one
end to the remote I/O side to form a Faraday cage.
If an open-circuit occurs during voltage measurement (the line is not monitored), any input
signals are processed on the high-resistance inputs. The value resulting from this
fluctuating input voltage is not reliable; with voltage inputs, the channels must be terminated
with a 10 kΩ resistor. The internal resistance of the source must be taken into account.
For a current measurement with the shunt connected in parallel, the 10 kΩ resistor is not
required.
The analog inputs are designed to retain the metrological accuracy for 10 years. A
recalibration must be carried out every 10 years.
Reaction in the Event of a Fault
If the device detects a fault on an analog input, the AI.Error Code system parameter > 0 is
set. In case of module faults, the Mod. Error Code system parameter > 0 is set.
In both cases, the device activates the FAULT LED.
In addition to the analog value the the error code must be evaluated. The analog value
must be configured to ensure a safety-related reaction.
The error code allows the user to configure additional fault reactions in the user program.
Line Monitoring for Digital Outputs
The analog inputs (AI) of the F3 AIO 8/4 01 can also be used to monitor the line for open-
circuits and short-circuits of digital outputs of other HIMatrix controllers (line monitoring). To
this end, the transmitter supply must be set to 26 V. To do so, set the Transmitter
Voltage[01] parameter in SILworX and ELOP II Factory to 2. see Table 26 und Table 30.
Requirements
Using HIMatrix devices with analog inputs, the digital outputs of any HIMatrix controller can
be monitored under the following conditions:
The transmitter supply of analog inputs exists,
An external shunt can be connected to the analog inputs.