Product Description
The X-DI 32 51 standard module is a digital input module and it is intended for use in the
programmable electronic system (PES) HIMax.
The module can be inserted in any of the base plate slots with the exception of the slots
reserved for system bus modules. For more information, refer to the System Manual
(HI 801 001 E).

The module is used to evaluate up to 32 digital input signals.
The standard module can be operated with safety-related modules within one base plate.
The standard module is non-reactive to the safety-related modules. In particular, this
includes EMC, electrical safety, communication to the X-SB and X-CPU modules and the
user program.
Module and connector boards are mechanically coded, see Chapter 3.6.1. This measure
ensures that a safety-related module cannot be replaced by a standard module.
Refer to the HIMax Safety Manual (HI 801 003 E) for more information on the standards
used to test and certify the modules and the HIMax system.
Safety Function
The module does not perform any safety-related functions.
The module evaluates the digital input signals and provides them to the user program.
The parameters and status for this module must not be used for safety functions.
Reaction in the Event of a Fault
If a fault occurs, the assigned input variables transmit the initial value to the user program.
The initial values must be set to 0 to ensure that the input variables transmit the value 0 to
the user program if a fault occurs.
The module activates the Error LED on the front plate.
Scope of Delivery
The module must be installed on a suitable connector board to be able to operate. If a FTA
is used, a system cable is required to connect the connector board to the FTA. Connector
boards, system cables and FTAs are not included within the scope of delivery.
The connector boards are described in Chapter 3.6. the system cables are described in
Chapter 3.7. The FTAs are described in own manuals.
Structure
The module has 32 digital inputs (24 V) for digital signals, contact makers and proximity
switches (two-wire or three-wire). For detecting a high level on the digital input, the voltage
and current thresholds must be exceeded, see Table 8.
The eight short-circuit-proof supplies feed four supply outputs each (S1+ to S8+). One
supply output is assigned to each digital input.
The processor system for the I/O module controls and monitors the I/O level. The data and
states of the I/O module are made available to the processor modules via the redundant
system bus. The system bus has a redundant structure for reasons of availability.
Redundancy is only ensured if both system bus modules are inserted in the base plates
and configured in SILworX.