The ELX2008 digital output terminal enables the direct connection
of intrinsically safe actuators located in hazardous areas classified
zone 0/20 or 1/21. The ELX2008 supplies an output voltage of 24
V DC and a maximum output current of 30 mA per channel.

The signal state of each channel is indicated by a light emitting diode.
EtherCAT terminals of the ELX series must always be operated in
conjunction with the ELX9560 power supply terminal. This terminal
generates an electrically isolated output voltage (24 V EX) from the
input voltage (24 V DC) for supplying the subsequent ELX terminals.
If a new power supply is required, the combination of an ELX9410
and an ELX9560 can be used so that further ELX terminals can be
added.
The ELX terminal segment must be terminated with one ELX9012.
two ELX9410 or one EK1110. The use of two ELX9410 allows the
use of EL terminals behind ELX terminals. With the EK1110. the
terminal segment can be continued via an EtherCAT cable,
for example to implement cable redundancy.