Be careful when unpacking the ProTech® 203 system. Check the device for signs
of damage such as a bent or dented case and loose or broken parts. If damage
is found, notify the shipper immediately. The device may be stored in its original
shipping container until it is ready for installation. Protect the device from weather
and from extreme humidity or temperature fluctuations during storage.
Carefully study this chapter before choosing a location for the ProTech 203
system. Wiring and grounding considerations may influence the selection of a
location for the device.

Multiple chassis systems using MicroNet power supplies may have power supplies of the same model,
but in different chassis, connected to the same source. In this case, each branch to a chassis must have
its own overcurrent protection sized according to Table 4-4. and the power source must be sized for the
sum of the branches.
Input Power Wiring
MicroNet controls require a fixed wiring installation for ac applications. Ground leakage exceeds 3.5 mA
AC. Maximum ground leakage for ac installations is 7.2 mA at 60 Hz. A ground conductor connected to
the chassis is required for safety. The power supply grounding terminal(s) should also be connected to
earth to ensure grounding of the power supply printed circuit boards. The grounding conductor must be
the same size as the main supply conductors.