The MVI69 EtherNet/IP™ Client/server Communication Module allows CompactLogix™ /
MicroLogix™1500 LRP processors to interface easily with EtherNet/IP protocol compatible
devices and hosts. Devices commonly supporting the protocol include PLCs, PACs, field
devices, and host HMI systems.
The module can send read or write commands to remote devices on the EtherNet/IP
network. The module also has 20 servers that allow the module to receive commands from
remote devices. Up to 100 commands can be configured by the user. The Module provides
support for an Ethernet port to be used in applications requiring a separate or dedicated
network.

Features
Benefits
High Data Throughput
High-speed data transfer between MVI69 module and CompactLogix / MicroLogix 1500 LRP
processor
Installs as a generic 1769 module, sample ladder logic and AOI included
View module data and status in RSLogix™ 5000 controller tags and UDTs
EtherNet/IP™ Client and Server
Integrate with widely available Rockwell Automation and 3rd party products.
Client/server Explicit Messaging communication supported
20 server connections
Client connection supporting 100 communication commands
In-chassis Solution
Bridge to optimize data throughput while communicating with HMI or SCADA and other
control platforms without losing valuable process control bandwidth
Configuration
ProSoft Configuration Builder (PCB) provides a PC-based software configuration solution
for quick and easy management of module configuration files, as well as viewing
communication and network diagnostics. PCB is not only a powerful solution for new
configuration files, but also allows you to import information from previously installed
(known working) configurations into new projects.
Functional Specifications
Provides up to 4000 16 bit memory registers for user application data transfer
User-definable module memory usage
10/100 Base-T Ethernet compatible interface
Functions as a server and a Client
Status data is available in ladder logic or through the Configuration (CFG) Serial
Port
Server Specifications
Supports EtherNet/IP explicit, connected, and unconnected class messaging
20 independent server connections permit remote clients to interact with all data
contained in the module
Data can be derived from other clients on the network, through the client on the
module, or from the CompactLogix processor
Client Specifications
Actively issues connected, explicit messages to other nodes on the network
Supports 100 user-defined commands from a single client
Allows command control from ladder logic
General Specifications
Single-slot, 1769 backplane-compatible
The module is recognized as an Input/Output module and has access to processor
memory for data transfer between processor and module.
Ladder Logic is used for data transfer between module and processor. A sample
ladder file with AOI is included.
Configuration data obtained from configuration text file downloaded to module. A
sample configuration file is included.
Supports CompactLogix and MicroLogix 1500LRP processors with 1769 I/O bus
capability and at least 800 mA of available 5 VDC backplane current.