MTL4546S ISOLATING DRIVER
for 4–20mA HART® valve positioners with line fault detection and long field lines
The MTL4546S accepts a 4/20mA floating signal from a safe-area
controller to drive a current/pressure converter (or any other load up to
710Ω) in a hazardous area. For HART valve positioners, the module also
permits bi-directional transmission of digital communication signals.
Process controllers with a readback facility can detect open circuits in
the field wiring: if these occur, the current taken into the terminals drops
to a preset level. The reduced maximum open-circuit voltage permits
the use of longer field lines compared to MTL4546

SPECIFICATION
See also common specification
Number of channels
One
Location of I/P converter
Zone 0. IIC, T4–6 hazardous area if suitably certified
Div. 1. Group A, hazardous location
Working range
4 to 20mA
Digital signal bandwidth
500Hz to 10kHz
Maximum load resistance
710Ω (14.2V at 20mA)
Minimum load resistance
90Ω
Output resistance
> 1MΩ
Under/over range capability
Under range = 1mA
Over range = 24mA (load ≤ 520Ω)
Input and output circuit ripple
< 40µA peak-to-peak
Transfer accuracy at 20°C
Better than 20µA
Temperature drift
< 1.0µA/°C
Input characteristics
Response time
Settles within 200µA of final value within 100ms
Communications supported
HART
LED indicator
Green: power indication
Maximum current consumption (with 20mA signals into 250Ω load)
35mA at 24V dc
Power dissipation within unit (with 20mA signals into 250Ω load)
0.8W at 24V
Safety description
Vo
=22V Io
=100mA Po
=550mW Um = 253V rms or dc