Product specifications
Description
The ibaLink-SM-64-SD16 board serves as the direct optical interface between the
SIMADYN D automation system and the ibaPDA/ibaScope process data acquisition sys
tem or the ibaLogic automation system.
The ibaLink-SM-64-SD16 board features an optical bidirectional channel that can transmit
64 analog and 64 binary signals simultaneously in both directions in one millisecond.
The connection to ibaPDA/ibaScope or ibaLogic is carried out by connecting ibaFOB-4i or
ibaFOB-io PC interface boards.
The board can be directly installed in a SIMADYN D rack and behaves there just like a
standard SIMADYN D board.

Driver
Driver 1: CS3 for STRUC version 3:
This variant acts like a CS3 MMC communication board with the following properties:
The board can only be used in sub-racks with C-bus connection (i. e. SR12 or
SR24. or SR1 and SR5. respectively)
The board can only communicate with P16 processor modules that have the C-bus
connection, i.e. not with the technology processors (e.g. PG16. PG26. PS16.
PT20/G/M)
The board features a dual-port RAM (DPR) with a memory capacity of 16 KB
The MMC "COMNET" protocol is used as the communication protocol. All data is
exchanged, including initialization tasks and monitoring functions, according to this
protocol.
Driver 2: CS12 for STRUC version 4:
This variant acts like a CS12 fiber-optic interface module with the following properties:
The board can only be used in sub-racks with C-bus connection (i.e. SR12 or
SR24)
The board can also communicate with P32 processor modules. The P32 proces
sors are all equipped with a C-bus connection
The board features a dual-port RAM (DPR) with a memory capacity of 32 KB
The CIP3 protocol is used as the communication protocol. All data is exchanged,
including initialization tasks and monitoring functions, according to this protocol
Regardless of the variants of the drivers and the STRUC-version, the board is well em
bedded in the SIMADYN D environment:
Data is exchanged in SIMADYN D with standard modules.
The board is initialized with a standard central module.
SIMADYN D and the iba system connected can be switched on and off fully inde
pendent of each other. SIMADYN D can also run without the iba system connected
and visa versa
The execution cycle in the ibaLink-SM-64-SD16 is 1 ms
Note
The iba FOB-SD interface board is available for STRUC V4/P32 systems for transmitting
large data volumes with optional access; this PC interface board communicates with the
SIMADYN D CS12/13/14 interface module.