• For For Foundation™ fieldbus networks in hazardous areas
• Redundant configuration for super-high system availability
• Complete enclosure systems for up to 6 intrinsically safe spur connections
• Failure alarm direct to host control system via integrated fieldbus device
• Mount in Zone 1 (gas) or 21 (dust) with spurs connected into Zone 0
• Compatible with FISCO and Entity certified fieldbus instruments
• Ergonomic mechanical design
• Pluggable system components, without ‘gas free’ constraints
• Optional, integrated surge protection for trunk and spurs

The 9372-FB Redundant Fieldbus Barriers are field-mounted wiring
hubs that create up to six intrinsically safe spur connections
from a high-energy trunk, for connection to suitably certified
Foundation™ fieldbus H1 instruments. They may be installed in
Zone 1 (gas) or Zone 21 (dust) hazardous areas, with the trunk
wiring implemented using suitably protected cable and increased
safety (Ex e) connection facilities.
Each enclosure system uses duplicated Fieldbus Barrier
modules in a redundant configuration to achieve significantly
higher system availability than equivalent ‘simplex’ units.
The 9372-FB may therefore be selected for critical process
applications where failure of the Fieldbus Barrier would
otherwise result in unacceptable downtime or lost production.
It is also ideal for use in Fieldbus Safety Instrumented Function
(SIF) networks in which nuisance trips cannot be tolerated.
Failure annunciation to the host control system is provided by
means of an integrated Foundation™ fieldbus device with Digital
Input Function Block capability.
In common with conventional Fieldbus Barriers, each
intrinsically safe spur is capable of supporting a FISCO or ‘Entity’
certified fieldbus device located in a Zone 0 or 1
hazardous area. The short-circuit protected spurs are
galvanically isolated from the trunk and require no protective
ground connection in the field.
The 9372-FB redundant fieldbus barrier is based on our
revolutionary 9370-FB range of products, which are supplied
as complete, factory-assembled enclosure systems that do not
require additional wiring, customised housings or complex
ancillary components. Electrical and mechanical aspects of the
design are integrated, providing the industry’s first complete,
ergonomic solution for ‘High Energy Trunk’ applications in
hazardous areas.
Uniquely, the key modular components of the system (Fieldbus
Barrier, Terminator and Surge Protectors) may be ‘hot-plugged’
by design and without gas-clearance procedures or separate
isolating switches. This virtually eliminates the risk associated
with hazardous area maintenance activities, speeds module
replacement and avoids the need for specialist operator training.
Optional features include pluggable surge protection
components for the fieldbus trunk and individual spurs.
Connection facilities with generous room for cable management
are provided within the Fieldbus Barrier enclosure for the trunk
and spur wiring.
For added flexibility, a redundant-capable enclosure can be
specified part-populated with one 6-spur module (model
no. 9375-FB). This permits future upgrading from simplex to
redundant mode simply by plugging in an additional Fieldbus
Barrier module and optional alarm module.
The 9372-FB Fieldbus Barrier is bus powered and requires no
additional power supply in the field. When used with a fieldbus
host control system, power for the trunk may be provided by
redundant power supplies.
wechat/whatsapp:
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved