Product Description
The safety-related F3 AIO 8/4 01 remote I/O is a compact system located in a metal
enclosure with 8 analog inputs and 4 analog outputs.
The remote I/O is available in three model variants for SILworX and three model variants
for ELOP II Factory, see Chapter 3.3. All variants are described in this manual.
The remote I/O serves as extension of the I/O level of HIMax and HIMatrix controllers, and
is connected to them via safeethernet. The remote I/O itself is not able to run a user
program.

The HIMatrix remote I/Os are not multi-master capable.
The remote I/O is suitable for mounting in Ex-zone 2. see Chapter 4.1.3.
The device has been certified by the TÜV for safety-related applications up to SIL 3 (IEC
61508. IEC 61511 and IEC 62061), Cat. 4 (EN 954-1) and PL e (EN ISO 13849-1). Further
safety standards, application standards and test standards are specified in the certificate
available on the HIMA website.
Safety Function
The remote I/O is equipped with safety-related analog inputs. The input values on the
inputs are safely transmitted to the connected controller via safeethernet. The outputs are
safely assigned their values by the connected controller via safeethernet.
Safety-Related Analog Inputs
The remote I/O is equipped with 8 analog inputs with transmitter supplies for the unipolar
measurement of voltages, referenced to L-.
The remote I/O is intended to measure the voltage on the inputs. To measure the current
on the inputs, connect a resistor of up to 500 Ω in parallel to each input.
Only shielded cables with a length of a maximum of 300 m must be connected to the
analog inputs. Each analog input must be connected to a twisted pair of wires. The
shielding must be connected to the remote I/O and the sensor housing and earthed of one
end to the remote I/O side to form a Faraday cage.
If an open-circuit occurs during voltage measurement (the line is not monitored), any input
signals are processed on the high-resistance inputs. The value resulting from this
fluctuating input voltage is not reliable; with voltage inputs, the channels must be terminated
with a 10 kΩ resistor. The internal resistance of the source must be taken into account.
For a current measurement with the shunt connected in parallel, the 10 kΩ resistor is not
required.
The analog inputs are designed to retain the metrological accuracy for 10 years. A
recalibration must be carried out every 10 years.
ALSTOM 029.076164 PC BOARD MODULE
Alstom Safety Hard Hat Application Engineering
ALSTOM MOTPRO MCHNM PROTECTION RELAY MCHNM01H1AB0500A
GEC ALSTOM RFC15001006A POWER SUPPLY MODULE
GEC ALSTOM KBCH13001H15MEL Transformer Differential Protection Relay KBCH
ALSTOM CEGELEC ALSPA 20X4264/60C , 20X4264A1L
Alstom Low Burden Tripping Relay MVAJ13L1GB0771A
ALSTOM MVAJ105RA0802A Protection Relay
Micom Alstom P143 Feeder Management Relay P143311A1A0040A
CONVERTEAM 029.211-759 / 029211759
CONVERTEAM 8321-6002 / 83216002
CONVERTEAM 029.223-006 / 029223006
CONVERTEAM 029.226681 / 029226681
Alstom 70B002 Pcb Circuit Board Rev B
| User name | Member Level | Quantity | Specification | Purchase Date |
|---|
wechat/whatsapp:
+86-181-44100-983
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved