Line control is used to detect short-circuits or open-circuits, e.g., on EMERGENCY STOP inputs
complying with Cat. 4 and PL e in accordance with EN ISO 13849-1. Line control can be
configured for the F60 system.
The digital outputs are pulsed. This allows monitoring of the wires to the digital inputs of the
F60 DI 32 01 or F60 DIO 24/16 01 module.
The safety-related F3 AIO 8/4 01 remote I/O is a compact system located in a metal
enclosure with 8 analog inputs and 4 analog outputs.
The remote I/O is available in three model variants for SILworX and three model variants
for ELOP II Factory, see Chapter 3.3. All variants are described in this manual.
The remote I/O serves as extension of the I/O level of HIMax and HIMatrix controllers, and
is connected to them via safeethernet. The remote I/O itself is not able to run a user
program.
The HIMatrix remote I/Os are not multi-master capable.
The remote I/O is suitable for mounting in Ex-zone 2. see Chapter 4.1.3.
The device has been certified by the TÜV for safety-related applications up to SIL 3 (IEC
61508. IEC 61511 and IEC 62061), Cat. 4 (EN 954-1) and PL e (EN ISO 13849-1). Further
safety standards, application standards and test standards are specified in the certificate
available on the HIMA website.
The DI 32 01 is a module with 32 digital inputs and is used for the modular F60 system. The
inputs are galvanically separated to the I/O bus.
The module can be inserted in the F60 subrack's slot 3...8. Slots 1 and 2 are reserved for the
power supply module and central module, respectively.
The module has been certified by the TÜV for safety-related applications up to SIL 3
(IEC 61508. IEC 61511 and IEC 62061), Cat. 4 and PL e (EN ISO 13849-1) and SIL 4
(EN 50126. EN 50128 and EN 129).
Further safety standards, application standards and test standards are specified in the
certificates available on the HIMA website.
Safety Function
Safety-Related Inputs
The module is equipped with safety-related inputs.The module is equipped with safety-related
inputs. These inputs are divided in 4 groups of 7 inputs and 1 group of 4 inputs (I29...I32). Refer
to Table 10 for more information about terminal assignment. Each group is equipped with a
common short-circuit-proof supply LS+.
Reaction in the Event of a Fault
If the module detects a fault on a digital input, the user program processes a low level in
accordance with the de-energized to trip principle.
The module activates the ERR LED.
In addition to the channel signal value, the user program must also consider the corresponding
error code.
The error code allows the user to configure additional fault reactions in the user program.