The ELX3202-0090 analog input terminal allows the direct connection of
RTDs located in hazardous areas classified zone 0/20 or 1/21.
The circuitry of the ELX3202-0090 can operate sensors with 2-, 3- and
4-wire technology. Linearization is carried out over the entire freely
selectable temperature range. By default the terminal is set to Pt100
sensors with 3-wire technology. The ELX3202 0090 terminal indicates
signal state and sensor malfunctions (e.g. wire breakage) by means of
LEDs.

With the aid of the TwinSAFE SC technology (TwinSAFE Single Channel)
it is possible to make use of standard signals for safety tasks in any network
or fieldbus. To do this, EtherCAT I/Os from the areas of analog input,
position measurement or communication (4… 20 mA, incremental encoder,
IO-Link, etc.) are extended by the TwinSAFE SC function. The properties
typical for the signals and the standard functions of the I/O components
are retained. TwinSAFE SC I/Os differ optically from standard I/Os by a
yellow stripe on the front of the housing.
The TwinSAFE SC technology enables communication via a TwinSAFE
protocol. These connections can be distinguished from the usual secure
communication via Safety over EtherCAT.
The data from the TwinSAFE SC components is fed via a TwinSAFE protocol
to the TwinSAFE Logic, where it can be used in the context of safety-
relevant applications. Detailed examples confirmed/calculated by the TÜV
SÜD for the correct application of the TwinSAFE SC components and the
respective normative classifications can be found in the TwinSAFE
application manual.