The DGC-2020HD provides integrated engine-genset control, protection,
and metering in a single package. Microprocessor-based technology
allows for exact measurement, setpoint adjustment, and timing functions.
Front panel controls and indicators enable quick and simple DGC-2020HD
operation. A backlit liquid crystal display (LCD) can be viewed under a wide
range of ambient light and temperature conditions.
Basler Electric communication software (BESTCOMSPlus®) allows units to
be easily customized for each application. Because of the low sensing burden
in the DGC-2020HD, dedicated potential transformers (PTs) are not required.

These expansion modules eliminate the need for expensive external devices
by providing additional contact and analog inputs and outputs to certain
Basler Electric products.
Current Boost Module
The Current Boost Module rectifies the ac current received from the CTs
and provides dc current boost to the generator exciter field.
During normal generator operation, power from the generator output
provides sufficient exciter field power and the CBS 212A remains dormant.
During normal operation, the CTs are effectively shorted by the internal
SCRs of the CBS 212A. Normal generator operation is indicated by the
Operating Point Indication LED being lit.
If the generator output voltage decreases below the operating-point setting,
the CBS 212A detects the voltage drop, turns off the Operating Point Indication
LED, and removes the SCR “short-circuit” from the CTs.
The CBS 212A then provides full current boost to the generator exciter until
the voltage returns to a level just above the operating point setting.
The Controls and Indicators and Installation chapters provide information
about setting the Operating Point Adjustment.
An adjustable voltage limiting circuit prevents the Current Boost Module
output from exceeding the specified percentage of the nominal output
voltage (60. 120. or 220 Vdc). The Output Limit Select Jumpers are used
to select the nominal output voltage (60. 120. or 220 Vdc) and the Output
Limit Adjustment is used to set the desired percentage of the nominal output
voltage. The Output Limit Adjustment is adjustable over a range of 50 to
100 percent of the jumper-selected nominal output voltage.
The CBS 212A Current Boost System assists Basler SSR-series voltage
regulators during generator overload conditions and supplies the exciter
field during generator short-circuits. When used with three wire or 4-wire
generators, the CBS 212A supports sustained single-phase and multiple
-phase, line-to-line faults.
In addition, the CBS 212A permits four-wire generators to support A-phase
and B-phase line-to neutral faults.
The CBS 212A assembly consists of a Current Boost Module and two
current transformers (CTs). The Current Boost Module is designed for
behind-the-panel mounting.
An Operating Point Adjustment control and Operating Point Indication LED
are located on the front panel of the Current Boost Module.
An Output Limit Adjustment control is located on the bottom panel of the
Current Boost Module.
Special power CTs connect to two phases of the generator output and
provide current to the Current Boost Module. The Installation chapter
provides details about CT selection.
The IDP-801 Interactive Display Panel is a 7.5 inch/19 centimeter (measured
diagonally) color touchscreen interface that enables a user to monitor and
control a Basler Electric DECS-based excitation system.
IDP-801 monitoring and control features include DECS and excitation system
status, system control operations, and routine adjustments of the excitation
setpoint. The IDP-801 is compatible with DECS-250. DECS-250N, DECS-250E,
DECS-400. and DECS-450 Digital Excitation Control Systems.
DECS and synchronous machine system parameters are viewed and controlled
through interactive pages displayed by the IDP-801. Pages are organized according
to system functions. Navigation between pages and control of functions is achieved
by touching buttons located on the IDP-801 pages.
| Basler Electric BE1-25 M9FA6PN4N0F / BE125M9FA6PN4N0F |
| Basler Electric BE1-50/51B-235 / BE15051B235 Self-Powered Time Overcurrent Relay |
| Basler Electric PLA2400-12GM / PLA240012GM |
| Basler Electric DECS 125-15-B2C5 DIGITAL EXCITATION CONTROL SYSTEM |
| Basler Electric BE1-851 Overcurrent Relay H5A2S1N |
| Basler Electric BE1-59N A6EE1JC0N1F Ground Fault Overvoltage Relay |
| Basler Electric BE3-25-1S1N4 / BE3251S1N4 Synchronizing Check Relays |
| Basler Electric L304KC / L304KC Camera Interface |
| Basler Electric SCA1300-32FC / SCA130032FC |
| Basler Electric BE1-27 A3EE1JA1N6F Voltage Relay |
| Basler Electric BE1-51 G1EZ1PA1N0FY Time Overcurrent Relay |
| Basler Electric 9073800-103 Power Supply 110/120v-ac 12.8a Amp 15v-dc |
| Basler Electric Relay BE1-50/51B-207 Overcurrent Relay |
| Basler Electric BE1-51-H5EZ2PB1N0F / BE151H5EZ2PB1N0F Time Overcurrent Relay |
| Basler Electric BE1-32-A1E-E1C-B0N0F / BE132A1EE1CB0N0F |
| Basler Electric BE1-81O/U T3ED1JB7N0F (AS PICTURED) NSNP |
| Basler Electric DGC-2020 Digital Genset Controller 100-480v-ac |
| Basler Electric SSR 63-12 Static Voltage Regulator 63VDC 100-139 VAC |
| User name | Member Level | Quantity | Specification | Purchase Date |
|---|
wechat/whatsapp:
+86-181-44100-983
Email: kongjiangauto@163.com
Copyright © 2009 - 2026 Cld , All Rights Reserved K-JIANG All rights reserved