The IC693 Redundant Power Supply System consists of a Baseplate and an Adapter, described below.
Redundant Power Supply (RPS) Baseplate The Redundant Power Supply Baseplate
has slots for two standard IC693 power supplies, an attached adapter
connection cable that connects to the Power Supply
Adapter, status LED lights, a 24VDC user output, and status relay outputs.
There are two models of RPS
Baseplates, which are identical except for the length of the adapter connection cable.
The IC693ACC340 has a 0.125-meter cable, and the IC693ACC341 has a 0.6-meter cable.
Redundant Power Supply Adapter The Redundant Power Supply Adapter plugs into a
standard IC693 PLC baseplate’s power supply slot.
It has a connector that mates to the RPS Baseplate’s adapter connection cable.
It also contains the backup battery and serial port connector for the PLC (backup battery and
serial port connector are not functional on the individual power supplies).
Auxiliary I/O Wiring and Functional Descriptions
The Auxiliary I/O connector includes a number of diverse signals used to interface the S2K
controller to your motion controller and machine. The functions available include:
• Analog Command Input (AI1)
• Torque Limit Analog Input (AI2)
• Analog Output (AO)
• +5 Vdc Output (for auxiliary encoder) (on the Pulse Input on SSI216. SSI228. & SSI420 models)
• +12 Vdc Output (for Enable input)
• Enable Input
• OK Output
• Encoder Output
• Auxiliary Encoder Input (on the Pulse Input on SSI216. SSI228. & SSI420 models)
The SSI216. SSI228. & SSI420 models have a different configuration for the Discrete I/O
and Auxiliary I/O connections as shown on the connection diagrams in Section 3.6.10.
The Enable input and OK output may be wired for either sinking or sourcing operation. The
operational voltage range is 12 to 24 volts DC. The OK output can sink or source 100 mA
maximum. The wiring to the Auxiliary I/O connector should be of appropriate size and
insulation quality for the application. To meet the requirements of EN61000-4-5 and CE
mark, Auxiliary I/O cables shall be shielded and shall not exceed 30 meters in length.
We have the same series of models in stock.
If you don't find the model you need, please contact us and we will provide you with an official quotation!
GE IC800SSI107D2-CE S2K Series Standalone Motion Controller
GE IC800SSI107P2- CE VersaMotion S2K controller
GE IC800SSD107RS1-CC VersaMotion S2K controller
GE IC800SSI107RS1-CE S2K Series Standalone Motion Controller
GE IC800SSI107RD2-CE VersaMotion S2K controller
GE IC800SSI107RP2-CE VersaMotion S2K controller
GE IC800SSI104RP2-CE VersaMotion S2K controller
GE IC800SSD228S1-CC VersaMotion S2K controller
GE IC800SSI228D2-CE VersaMotion S2K controller
GE IC800SSI228P2-CE VersaMotion S2K controller
GE IC800SSD228RS1-CC VersaMotion S2K controller
GE IC800SSD107S1-CC VersaMotion S2K controller
GE IC800SSI107S1-CE S2K Series Standalone Motion Controller
User name | Member Level | Quantity | Specification | Purchase Date |
---|
wechat/whatsapp:
+86-181-4410-0983
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved