Command 3 provides the following variables:
• Primary variable – analog input in % or mA
• Secondary variable – travel target (valve set point) in % of ranged travel
• Tertiary variable – output pressure in psig, bar or kPa
• Quaternary variable – travel in % of ranged travel
To enable burst mode, select Mode > Burst > Burst Enable. To send a burst mode command,
select Burst Command. Burst mode must be enabled before you can change the burst
mode command.
General Information
Follow the prompts on the handheld communicator to enter or view information in the
following fields:
• HART Tag – Enter an up to 8 character HART tag for the instrument. The HART tag is the
easiest way to distinguish between instruments in a multi-instrument environment. Use
the HART tag to label instruments electronically according to the requirements of your
application. The tag you assign is automatically displayed when the Field Communicator
establishes contact with the digital valve controller at power-up.
• Message – Enter any message with up to 32 characters. Message provides the most
specific user-defined means for identifying individual instruments in multi-instrument
environments.
• Descriptor – Enter a descriptor for the application with up to 16 characters. The descriptor
provides a longer user-defined electronic label to assist with more specific instrument
identification than is available with the HART tag.
• Date – Enter a date with the format MM/DD/YY. Date is a user-defined variable that provides
a place to save the date of the last revision of configuration or calibration information.
• Valve Serial Num – Enter the serial number for the valve in the application with up to
12 characters.
• Inst Serial Num – Enter the serial number on the instrument nameplate, up to
12 characters.
• Polling Address – If the digital valve controller is used in point-to-point operation, the
Polling Address is 0. When several devices are connected in the same loop, such as for split
ranging, each device must be assigned a unique polling address. The Polling Address is
set to a value between 0 and 15. To change the polling address, the instrument must be
Out Of Service.
For the handheld communicator to be able to communicate with a device whose polling
address is not 0. it must be configured to automatically search for all or specific connected
devices.
• LUI Language – Select the language to be displayed on the local user interface; English,
French, German, Italian, Spanish, Chinese or Japanese.