Fault and Disturbance Recording
The advanced disturbance and event
recording features within the M60 can
significantly reduce the time needed for
postmortem analysis of power system
events and the creation of regulatory
reports. Recording functions include:
• Sequence of Event (SOE) - 1024 time stamped events
• Oscillography - 64 digital & up to 40 analog channels - Events up to 45s in length
• Data Logger and Disturbance Recording - 16 channels up to 1 sample/cycle/channel
The very high sampling rates and the large
amount of storage space available for
data recording in the M60 can eliminate
the need for installing costly stand-alone
recording equipment.
Cyber Security –
CyberSentry UR
CyberSentry UR enabled UR devices deliver
full cyber security features that help
customers to comply with NERC CIP and
NIST® IR 7628 cyber security requirements.
This software option delivers the following
core features:
AAA Server Support (Radius/LDAP)
Enables integration with centrally
managed authentication and accounting
of all user activities and uses modern
industry best practices and standards that
meet and exceed NERC CIP requirements
for authentication and password management.