Multibus Communication Module SCSI
Basic Station
The basic station operates in either automatic (closed) or manual (open) loop control. The operator manipulates the process
by means of the faceplate pushbuttons. The station interfaces
into the customer process by different means while in automatic or manual. In manual (open loop control),
the SAC station manipulates the control output by updating the MFP
module with control output values that are written to the CIS
module that drives the analog output. The set point value can
be modified and goes to the MFP module in every station
update message but has no effect on the process.
In automatic (closed loop control), the station operator generated set point value is used by the MFP module PID algorithms
to manipulate the process. The operator cannot establish a
control output value with the output raise/lower pushbuttons
while in automatic mode.
COMPUTER LEVEL
The computer level of supervisory control is used when a PID
control loop is directly supervised and controlled by an external supervisory computer program, not an operator. When the
station is at the computer level, the operator cannot change
the station mode, control output, set point, or ratio index values via the SAC station faceplate. However, the operator can
place the station to the local level by pressing the CMPTR or
MAN pushbutton on the SAC station faceplate.
When at the computer level, the control strategies (basic, ratio
and cascade) and the station modes (manual, automatic and
cascade/ratio) operate in the same manner as they do at the
local level. The only difference is that the station variables are
controlled by the external station interface.
The station function code (function code 80) operates a computer watchdog timer that must be started by the supervisory
computer program periodically. The watchdog timer is started
when the computer program changes the station mode, a station variable while at the computer level, or when it issues a
computer OK command at either level. When a watchdog timer
time-out occurs, the station reverts back to a predetermined
computer backup state.