BE1-87T Transformer Differential Relays provide primary protection for power
transformers and are available in either Single-Phase or Three-Phase
configurations. The solid-state BE1-87T compares the currents entering and
leaving the protected transformer. If a fault is detected, the relay initiates a trip
signal to isolate the power transformer. This limits damage to the transformer
and minimizes the impact on the power system.

BE1-87T relays use three types of restraint:
• Percentage of through-current
• Second harmonic
• Fifth harmonic
Selectivity in differential relaying is based on the ability to distinguish between
internal and external faults.
This is achieved by comparing the currents into and out of a power transformer.
Comparing these currents often requires more than two inputs.
For example:
• Power transformers may have a significant portion (greater than 10 %) of the
current flowing in a third or tertiary winding.
• Power transformers can have multiple breakers for a given winding (e.g., ring
bus or breaker and-a-half bus).
BE1-87T relays are available with up to five restraint inputs for the single-phase
unit and up to three restraint inputs per phase for the three-phase unit.
The SR8A Retrofit Voltage Regulator is an economical, direct replacement
for existing Basler Electric SR8A voltage regulators. Designed for brush
and brushless synchronous generators, it delivers precise voltage regulation,
fast response times, and dependable excitation control while fitting within
the same mounting footprint as the original SR regulator.
The retrofit package incorporates a modern AVC125-10 voltage regulator and,
where required, an internal sensing module, simplifying installation and
minimizing downtime.
Engineered for reliability in demanding power generation applications, the
SR8A Retrofit supports single- or three-phase sensing, voltage matching,
reactive droop compensation, line drop compensation, and underfrequency
protection. Its rugged design withstands harsh industrial environments,
while compatibility with accessories such as excitation limiters, power factor
controllers, and auto synchronizers makes it a versatile solution for generator
upgrades and modernization projects.
The MOC2XXX series of motor operated controls consists of a motor-driven,
variable potentiometer and the limit switches required to provide remote
adjustment of resistance or voltage. MOC2XXX controls can be specified for
ac or dc operation with 24-, 32-, 48-, or 120-volt control power.
MODEL NUMBER DEFINITION
The model number for this series of MOCs consists of the prefix MOC2
followed by three digits. The first digit establishes the input control voltage.
The second and third digits establish the output control element characteristics.
Table 1 lists the available model numbers and the corresponding operating
characteristics. For example, MOC2305 has a 32 Vdc control input and a 500
ohm, 2 watt potentiometer.The MOC2 Motor Operated Potentiometer is a
motor-driven control device
designed to provide remote adjustment of resistance or voltage in power
system and control applications.
The MOC series combines a variable potentiometer with integrated limit
switches, enabling precise remote control while ensuring dependable
operation. Available in configurations supporting AC or DC operation with
24 V, 32 V, 48 V, or 120 V control power, the MOC2 offers flexibility for a
wide range of installation requirements.
Ideal for generator control, excitation systems, and industrial power
applications, the MOC2 simplifies remote setpoint adjustment and enhances
operational convenience. Its robust design and versatile control power
options make it a reliable solution for applications requiring accurate and
repeatable voltage or resistance control from a remote location.

Basler Electric BE1-51 K1E Z1S B1C6F / BE151K1EZ1SB1C6F Time Overcurrent Relay |
Basler Electric 90-72300-114 / 9072300114 Motor Operated Control |
Basler Electric 9 1100 00 113 / 9110000113 Motor Operated Control |
Basler Electric MOC2, Motor Operated Potentiometer |
Basler Electric BE1-25 M1F A7P A5V6F Sync-check Relay |
Basler Electric Static Voltage Regulator SR32A2B05B3E |
Basler Electric SSR 63-12 Static Voltage Regulator 63VDC 100-139 VAC |
Basler Electric 9170206111 Protective Relay |
Basler Electric BEI-81 O/U Solid-State Protective Relay Module |
Basler Electric IFM-102 9324100102 Firing Circuit Chassis 120v-ac |
Basler Electric IFM-150 9333700122 Firing Circuit Chassis 120v-ac |
Basler Electric V6RAB / V6RAB |
Basler Electric BE1-51-K1E-Z1O-A0N0F / BE151K1EZ1OA0N0F Time Overcurrent Relay |
Basler Electric BE1-67N Directional Overcurrent Relay |
Basler Electric BE1-60 Voltage Balance Solid State Protective Relay B1FA1C1M1F |
Basler Electric BE1-87TE1EA1JD1N5F Transformer Differential Relay |
Basler Electric P/N: 90-72300-340 MODEL: MOC2199 POTENTIOMETER MOTOR OPERATED |