Data Highway Plus (DH+) channel offers:
• communication rates of 57.6 Kbaud, 115.2 Kbaud, and 230.4 Kbaud.
• maximum network length of 3048 m (10,000 ft) at 57.6 Kbaud
• Belden 9463 (blue hose) cable connection between nodes (daisy chain connection).
• built-in isolation.

Heat/Cool Minimum On-times
Words 6 and 8 for channel 1
These values determine the minimum cycle time after which loop
TPO bits will turn ON. They are used to allow contactors time to close
or pull in. If the contactor is energized for less than this value, the
contactor will not close, but the attempt will count as a cycle.
For example, suppose you set the TPO period for 10 seconds and the
minimum ON time to 1 second. Then if the module calculates a CV%
of 10% or less, the TPO bit for that zone will not turn ON.
Heat/Cool TPO Period
Words 7 and 9 for Channel 1
When CV loop output is time–proportioned (TPO), use this value to
set the interval between successive turn–ONs. For less than a 100%
output level, the output goes OFF for the balance of the interval.