All shielded cable must be twisted conductor pairs with either a foil or a braided
shield. All signal lines should be shielded to prevent picking up stray signals from
adjacent equipment. Connect the shields as shown in the plant wiring diagram
(Figure 2-1). Wire exposed beyond the shield must not exceed two inches. The
other end of the shield must be left open and insulated from any other conductor.
Do not run shielded signal wires with other wires carrying large currents. See
manual 50532. EMI Control in Electronic Governing Systems, for more
information.
Installations with severe electromagnetic interference (EMI) may require shielded
cable run in conduit, double shielded wire, or other precautions. Contact
Woodward for more information.

Up to two Remote RTN modules may be installed into each MicroNet Plus 8/14 expansion chassis (only
one RTN for 6/12 slot expansion chassis). When initialized by the main chassis CPU, the Remote RTN
modules will acquire either a SYSCON or STANDBY status. The Remote RTN module that becomes
SYSCON will control the expansion chassis where it is located. It will synchronize with the STANDBY
Remote RTN module and perform any redundancy functions as necessary. Input and output data from all
I/O modules will be managed appropriately and made available to the GAP Application running in the
main-chassis CPUs.