The TMR5200 Module is designed for 3-2-0 operation. A TMR system cannot operate with a single CPU.
This module was designed and rated for –40 to +85 °C operation in the industrial marketplace.
RTN Port
In a TMR5200 based system, each Kernel CPU provides Real Time Network (RTN) capability for
expanding to other racks using Ethernet port 4 (RJ45). This RTN port communicates between the main
chassis CPU's and any Remote RTN modules located in an expansion chassis. The GAP software
application defines the expansion racks, their I/O modules, and the use of the RTN port (GAP block is
RTN).

All shielded cable must be twisted conductor pairs with either a foil or a braided
shield. All signal lines should be shielded to prevent picking up stray signals from
adjacent equipment. Connect the shields as shown in the plant wiring diagram
(Figure 2-1). Wire exposed beyond the shield must not exceed two inches. The
other end of the shield must be left open and insulated from any other conductor.
Do not run shielded signal wires with other wires carrying large currents. See
manual 50532. EMI Control in Electronic Governing Systems, for more
information.
Installations with severe electromagnetic interference (EMI) may require shielded
cable run in conduit, double shielded wire, or other precautions. Contact
Woodward for more information.
| User name | Member Level | Quantity | Specification | Purchase Date |
|---|
wechat/whatsapp:
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved