Plant Loop to Plant Loop Transfer Module Manufacturers ABB, Bailey Model(s)
ABB Bailey Infi 90, ABB Bailey Infi 90 and Net 90
Additional Information This is a kit that includes the INSEM01, INNIS01, and INTKM01 modules along with the associated termination units and cables.
Estimated Shipping Size Dimensions: 3.0" x 7.0" x 12.0" (7.6 cm x 17.8 cm x 30.5 cm)
Weight: 1 lbs 16.0 oz (0.9kg )
Tariff Code: 8538907080
Country of Origin: United States Ships from Webster NY, USA
Plant Loop to Plant Loop Transfer Module
Symphony Harmony
IndustrialIT System 800xA
Overview
Features and Benefits
■ Extending the Return-on-Investment
of Harmony Systems. New hardware
and software product releases increase
operating efficiency and extend the
life of installed systems. New products and programs make the decision
to evolve existing systems straightforward and easy.
■ System 800xA Extends Harmony
System Functionality to Achieve
Greater Productivity Gains. System
800xA extends the reach of traditional
automation systems. When integrated
with Harmony systems, productivity
gains necessary to succeed in todayís
business world are achieved.
The IOR810 has the following features:
- Selectable redundant or non-redundant configurations
- Supports the Sequence of Events (SOE) function of the S800 I/O subsystem.
- Ability to interface with the following types of I/O in the S800 I/O subsystem: basic AI/AO, basic DI (contact input), SOE DI, basic DO,
Pulse inputs, temperature device inputs (RTDs and thermocouples), intrinsically safe,
and redundant I/O Table 5 lists the S800 I/O modules that have been validated for use with the IOR810.
The IOR810 provides an alternative way to use the S800 I/O with Sequence of Events (SOE) functionality.
The accuracy of the SOE timestamps is determined by the specifications of each S800 SOE digital input module type.
The IOR810 is the interface between the HN800 I/O bus (electrical or fibre optic) and the existing S800 I/O module bus (fibre optic only).
The core function of the IOR810 is to scan the S800 I/O modules and provide information to the Symphony Plus controller via the HN800.
The IOR810 connects and scans up to seven S800 cluster modems over the fibre module bus.
Each cluster modem can support up to 12 S800 I/O modules.
The distance between the IOR810 and the Symphony Plus controller is up to 30 metres if connected via the electrical HN800 bus;
If connected via a fibre optic HN800 bus, the distance between the IOR810 and the Symphony Plus
controller is up to 3000m using RFO810 repeaters.
If using plastic fibre optic cables, the maximum distance of the fibre optic modular bus between the
IOR810 and the S800 cluster modem or between two cluster modems in a daisy chain is 15 metres.