The high performance diff erential pressure transmitter
EJA110E features single crystal silicon resonant
sensor and is suitable to measure liquid, gas, or
steam fl ow as well as liquid level, density and
pressure. EJA110E outputs a 4 to 20 mA DC signal
corresponding to the measured diff erential pressure.
Its accurate and stable sensor can also measure the
static pressure which can be shown on the integral
indicator or remotely monitored via BRAIN or HART
communications. Other key features include quick
response, remote set-up using communications and
self-diagnostics. FOUNDATION Fieldbus, PROFIBUS
PA and 1 to 5 V DC with HART (Low Power) protocol
types are also available. EJA-E series models in
their standard confi guration, with the exception of
the Fieldbus, PROFIBUS and Low Power types,
are certifi ed as complying with SIL 2 for safety
requirement.

STANDARD SPECIFICATIONS
Refer to GS 01C31T02-01EN for Fieldbus
communication type and GS 01C31T04-01EN for
PROFIBUS PA communication type for the items
marked with “◊.”
□ PERFORMANCE SPECIFICATIONS
Zero-based calibrated span, linear output, wetted
parts material code S and silicone oil, unless
otherwise mentioned.
For Fieldbus and PROFIBUS PA communication
types, use calibrated range instead of span in the
following specifi cations.
Specifi cation Conformance
EJA-E series ensures specifi cation conformance to at
least ±3σ.
Reference Accuracy of Calibrated Span
(includes terminal-based linearity, hysteresis, and
repeatability)
□ FUNCTIONAL SPECIFICATIONS
Output “◊”
For 4 to 20 mA HART / BRAIN
(Output signal code D and J)
Two wire 4 to 20 mA DC output with digital
communications, linear or square root programmable.
BRAIN or HART FSK protocol are superimposed on
the 4 to 20 mA signal.
Output range: 3.6 mA to 21.6 mA
Output limits conforming to NAMUR NE43 can be
pre-set by option code C2 or C3.
For 1 to 5 V HART
(Output signal code Q)
Three or four wire low power 1 to 5 V DC output with
HART, linear or square root programmable.
HART protocol are superimposed on the 1 to 5 V DC
signal.
Output range: 0.9 V to 5.4 V DC
Failure Alarm
For 4 to 20 mA HART / BRAIN
(Output signal code D and J)
Analog output status at CPU failure and hardware
error;
Up-scale: 110%, 21.6 mA DC or more (standard)
Down-scale: −5%, 3.2 mA DC or less
For 1 to 5 V HART
(Output signal code Q)
Analog output status at CPU failure and hardware
error;
Up-scale: 110%, 5.4 V DC or more (standard)
Down-scale: −5%, 0.8 V DC or less
Damping Time Constant (1st order)
Amplifier damping time constant is adjustable from
0.00 to 100.00 s by software and added to response
time.
Note: For BRAIN protocol type, when amplifier software
damping is set to less than 0.5 s, communication
may occasionally be unavailble during the
operation, especially while output changes
dynamically. The default setting of damping
ensures stable communication.
Update Period “◊”
Differential pressure: 45 ms
Static pressure: 360 ms
Zero Adjustment Limits
Zero can be fully elevated or suppressed, within the
lower and upper range limits of the capsule.
External Zero Adjustment
External zero is continuously adjustable with
0.01% incremental resolution of span. Re-range
can be done locally using the digital indicator with
rangesetting switch.
Integral Indicator (LCD display, optional) “◊”
5-digit numerical display, 6-digit unit display and bar
graph.
The indicator is configurable to display one or up to
four of the following variables periodically.;
Measured differential pressure, differential pressure
in %, scaled differential pressure, measured static
pressure. See also “Factory Setting.”
Local Parameter Setting
(Output signal code D, J and Q)
Parameter configuration by the external zero
adjustment screw and push button (Integral indicator
code E) offers easy and quick setup for parameters
of Loop test, Tag number, Unit, LRV, URV, Damping,
Output mode (linear/square root), Display out 1. and
Re-range by applying actual pressure (LRV/URV)
and Device Information.
Burst Pressure Limits
69 MPa (10.000 psi) for wetted parts material S,
except for Measurement span F.
47 MPa (6.800 psi) for wetted parts material other
than S or Measurement span F.
Self Diagnostics
CPU failure, hardware failure, configuration error,