GENERAL
The ComfortPointTM Open Mixed I/O Module CPO-IO830A is
an independently mounted electronic module which is
designed for use in home (residential, commercial, and light
industrial) environments.
Specifically, it conforms with DIN 43880. with a max. slot
height of 45 mm, and is thus suitable for mounting in fuse
boxes. But it is also suitable for mounting on 35 mm standard
panel rails (both vertical and horizontal mounting possible).
The CPO-IO830A features a large complement of different
inputs and outputs which are automatically commissioned
(with firmware download) by the ComfortPointTM Open Plant
Controllers CPO-PC-6A, CPO-PC400. and CPO-PC200.

The CPO-IO830A communicated via the Panel Bus, and thus
employs the Panel Bus communication protocol. It can be
stationed up to 1.000 meters away from the controller (pro
vided it is then supplied with power by a separate, nearby
transformer).
The CPO-IO830A also features 20 inputs, 14 outputs, and 18
status LEDs. Up to 16 Mixed I/O Modules can communicate
with the controller.
The CPO-IO830A features both push-in terminals (for con
nection of other modules using the XS816 Bridge Connector)
and screw-type terminals.
Clearly visible LED control lamps convey important status and
alarm information.
The CPO-IO830A has a durable, anthracite-colored plastic
housing conforming with DIN 43880. It is thus suitable for
mounting in fuse boxes, but can also be mounted on 35 mm
standard panel rails (both vertical and horizontal mounting
possible).
FEATURES
• 24 Vac (+/- 20%) or 21…30 Vdc power supply (from
external transformer).
• Overvoltage protection: All inputs and outputs are
protected against overvoltages (24 Vac ± 20%; 30 Vdc)
as well as against short-circuiting.
• In the event of communication problems, the relay
outputs move to safety positions configured in
ComfortPointTM Open Studio.
• Push-in terminals for quick and convenient connec
tion to neighboring modules using the XS816 Bridge
Connector (regular cabling also possible).
• Status LED, service LED, power LED.
• Hex switch for setting Panel Bus address.
INTERFACES AND TERMINALS
The CPO-IO830A features an RS485 interface via which it
can communicate with other system components. This
interface employs the Panel Bus communication protocol.
Troubleshooting can be performed using the LEDs.