Features
• Powerful, flexible and field-customizable 16-channel analog input signal annunciator
unit
• A full choice of 26 standardized field selectable channel input signal types
• Four alarm/trip levels per channel; two low set and two high set points
• The last thirty events with time markings stored for local presentation
• Bar graph, curve or numerical display of set and measured parameter values
• Extensive data communication via the serial interface and the SPA bus
• Parameter selection and adjustment from front panel or via serial interface
• Sophisticated hardware and software self supervision system for maximum opera
tional reliability under the most demanding environmental conditions
• Powerful software support for parameterization of the relay, for reading measured
and recorded values, events, etc., and for storing readings
• Member of the SPACOM product family and ABB s Distribution Automation system
• CE marking according to the EC directive for EMC

Application
The analog annunciator unit is used in a variety of applications requiring monitoring of
analog quantities such as temperature, current, voltage, power, etc. in power plants,
substations and industry. The equipment is also used in off-shore installations. For tem
perature measurement standard Pt or Ni sensors are used. For measuring electrical
quantities measuring transducers with stan dard mA or V outputs are employed.
The annunciator units can be used as indepen dent stand-alone units, or they can be
inte grated via a fibre-optic bus to form complete supervision, event sequence reporting
and data acquisition systems.
Design
The channels of the analog annunciator unit measure voltage, current and resistance via
sensors or transducers in the process. Further, contact signals can be wired to the input
channels. The signal type can be separately set for each channel.
The channel inputs are galvanically separated from earth and from the digital part of the
annunciator electronics, but the channels are galvanically interconnected. This arrange
ment facilitates the supervision and the indication of earth faults in the transducers or the
transducer wiring.
The alarm channel inputs accept the following signal levels: 0 5 mA, 1 5 mA, 0 20 mA and
4 20 mA, 0 1 V, 0 5 V, 1 5 V, 0 10 V and 2 10 V. The following standard sensors types can
be used for temperature measurement: Pt 100. Pt 250.Pt 1000. Ni 100. Ni 120. Ni 250.
Ni 1000.
Further, any Pt or Ni signal within the range 65 1000 Ω, potentiometric signal within the
range 0 200 Ω, 0 500 Ω, 0 1 kΩ, 0 2 kΩ, 0 2.5 kΩ, 0 10 kΩ can be used and scaled.
For the resistance sensors two- or three-wire connection can be used.
In addition, the input channels can be activated by a making or a breaking contact.
The values measured can be shown as numerical values, bar graphs or curves on the dot
matrix display on the front panel. The same information can also be read by a superior
system via the serial interface.
The content of the event sequence register can be read on the display. The total system
can be configured by means of the push-buttons and the display on the front panel, or via
the serial interface.
When a measured signal exceeds or fallsbelow the set start value of the channel avisual
indication is obtained on the alarmpanel. At the same time the acoustic alarmoutput contact
picks up and, if configured, agroup alarm relay operates. The event thusgenerated is stored
in the event register.
Any information generated in the annunciatorunit can be read by a hierarchically superiorsystem
via the serial interface.
Data communication
The relay is provided with a serial interfaceon the rear panel. By means of a bus connection module
type SPA-ZC 17/S or SPAZC 21/S the relay can be connected to the fibre-optic SPA bus.
The bus connection module type SPA-ZC 21/S is powered from the host relay, whereas the bus
connection module SPA-ZC 17/S is provided with a