The G60 Tricon System Enclosure provides environmental
protection and housing for Triconex™ Tricon system chassis
and modules.
FEATURES
The G60 Tricon system enclosure offers the following features:
• Accommodates up to three Tricon system chassis
• Main power entry includes disconnect terminal
blocks for 120/240 V ac or 125 V dc systems, or
10 A, Type D, double pole circuit breakers for
120/240 Vac systems.
• Optional EMC/RFI line filters for redundant main
power (Triconex recommended).
• Vented enclosure for use in ordinary (IP 43) rated
environments

• Option for EMC compliance
• Compact design to minimize use of floor space
with both front and rear access that allows
maximum density of enclosures in a control room
environment
• Options for front and rear access or front access
only, both with optional safety glass front door
• Optional door intrusion monitoring
• Alarm contact terminal block assembly for main
chassis alarming, door intrusion monitoring
switches, enclosure temperature switch and field
power supply status.
• Bottom cable entry for power wiring and cables
for Triconex termination devices, such as External
• Termination Panels (ETPs), Field Terminations and
• External Termination Assemblies (ETAs)
• Conveniently placed eyebolts for transporting
and lifting the enclosures
• A 100 mm (4 in) plinth - total enclosure height of
2160 mm (85.0 in)
• Comfort handles with push-button/keylocks
Three earth (ground) points; two protective earth
(ground) studs, one isolated protective earth
(ground) rail and one isolated instrument earth
(ground) rail.
INTRODUCTION
The G60 enclosure is specifically designed for
housing Tricon system chassis and modules. It is
designed for use with the G61 or G66 Tricon
Termination Enclosures, and is available as a vented
enclosure only.
The G60 enclosure can be configured with up to
three Tricon chassis. Main power entry can include
optional EMC/RFI line filters. It is a free-standing,
floor mounted unit with an IP 43 rating for location in
mild (ordinary) environmental areas. A version is
available with optional EMC compliance.
NOTE
In regions that require EMC compliance, you
must order the EMC compliance option if
Tricon modules SMM or SRXM will be
installed in a chassis in this enclosure.
Without these modules, the enclosure
already fulfills the requirements for EMC
compliance.
The G60 enclosure, IP 43 rated, can be installed
bayed or adjoined to others to maximize the use of
floor space and ease of cabling. The enclosures can
be bayed together using third-party kits.
This enclosure and its configurations have been
tested and qualified by Invensys for use with the
Tricon chassis.
NOTE
It is possible to configure the G60 enclosure
with front access only and the safety glass
front door. However, since no ventilation is
located on a rear wall, the end-user is
responsible for locating adequate inlet
ventilation to maintain proper operation of
the enclosure’s equipment, through
ventilation on a side wall or from an adjoined
cabinet.
Vented enclosures have a limited thermal load (see
“Operating Temperatures (Ambient)” on page 8).
INGRESS PROTECTION
The metal enclosures provide the outer layer of
protection for the control electronics. Other layers are
provided by the module covers and built into the
modules. This approach to protection means that a
minimum of contaminants in the plant environment
reaches the control components, thus greatly
extending the life of the equipment.
DUAL THERMOSTAT
An optional dual (high/low) thermostat is available to
monitor enclosure temperature extremes.
DOOR INTRUSION MONITORING
An optional door intrusion monitoring switch is
available for each door on the enclosure. Each switch
is prewired to a set of alarm status terminal blocks.
wechat/whatsapp: