• 16 single-ended input channels
• Intrinsically safe field circuits
• Simple apparatus, dry contacts
or IS proximity detectors
• Open and short-circuit
field wiring detection
MODULE SPECIFICATION
See also System Specification
INPUTS
Number of channels
• 16
OFF current
• <1.2 mA
ON current
• >2.1 mA
Switching hysteresis
• 200 μA (nom.)
Applicable specifications
• NAMUR, DIN19234
Voltage applied to sensor
• 7.0 to 9.0 V from 1 kΩ ±10%
Output (wetting) current
• @ 100Ω line impedance
• >6 mA
Line fault detection
• Short circuit
• <100 Ω
• Open circuit
• >90 kΩ
Maximum input frequency in pulse counting mode
• 20 Hz
Minimum pulse width detected
• 45 ms
Peer to peer communication
SafetyNet Controllers can communicate with one another via Ethernet using SafetyNet
P2P - which has been certified as suitable for use in SIL 2 applications. Robust checks and
controls on access and data corruption ensure the safety of communication and
allow safety functions for which the inputs and outputs are widely separated to be
easily implemented - both in terms of the software programming and in the hardware design.
Open communications
MTL Open System Technologies products are just that - open. SafetyNet nodes
communicate with one another, with standard MOST nodes, historian and asset
management packages and with HMI packages over a fault tolerant Ethernet LAN,
running at up to 100 Mbit/s.
PAC8000 delivers full-specification performance in a broad range of harsh process environment conditions; extreme
temperatures, humidity or corrosives and conditions subject to shock and vibration.
In ATEX environments, PAC8000 also excels.
All components can be installed and maintained in Zone 2/Division 2 hazardous areas.
The I/O includes modules that can be connected directly to Intrinsically Safe (Exi) or Increased Safety (Exe) field wiring.
PAC8000 provides comprehensive diagnostic data on controllers, Bus Interface Modules (BIM),
I/O modules, field wiring and field instruments, allowing users to respond to issues quickly and effectively.
GE 8624-FT-IS Intrinsically Safe Field terminal with loop-disconnect
GE 8610-FT-NA Field terminal, non-arcing (Div 2)
GE 8625-FT-I SIntrinsically Safe Field terminal, THC
GE 8611-FT-FU Field terminal, non-arcing, fused (Div 2)
GE 8626-FT-IS Intrinsically Safe Field terminal, RTD
GE 8612-FT-NA 16-channel Field terminal, non-arcing
GE 8720-CA-04 4 module Intrinsically Safe carrier
GE 8710-CA-04 4 module carrier
GE 8723-CA-RB Railbus isolator carrier
GE 8711-CA-NS Node services carrier, screw terminal LAN
GE 8810-HI-TX 8-Channel Safety AI, 4-20mA with HART
GE 8117-DO-DC 8-channel DO, 2-60Vdc isolated, unpowered
GE 8811-IO-DC 8-Channel Safety DI/DO, 24VDC, module-powered
GE 8118-DO-AC 8-channel DO, 20-250Vac isolated, unpowered
GE 8201-HI-IS 8-channel Intrinsically Safe Analog Input, 4-20mA with Hart
GE 8204-AO-IS 8-channel Intrinsically Safe Analog Output, 4-20 mA
GE 8220-DI-IS 16-channel Intrinsically Safe Digital Input, switch/promixmity detector
GE 8205-TI-IS 8-channel Intrinsically Safe THC/mV input
GE 8601-FT-NI Field terminal, non-incendive (Div 2)
GE 8617-FT-NI Field Terminal, non-incendive, for 16 ch DI
GE 8602-FT-ST Field terminal, standard
GE 8618-FT-MT 16-pin Mass Termination Assembly (Div 2)
GE 8603-FT-FU Field terminal, non-incendive, fused (Div 2)
GE 8619-FT-MT 44-pin Mass Termination Assembly (Div 2)
GE 8604-FT-FU Field terminal, fused
GE 8620-FT-MT Field terminal assembly
GE 8605-FT-TC Field terminal, thermocouple
GE 8621-FT-IS Intrinsically Safe Field terminal, standard
GE 8606-FT-RT Field terminal, RTD
GE 8622-FT-IS Intrinsically Safe Field terminal, loop-disconnect (not for 8 channel DI)
GE 8607-FT-TC Field terminal, 8-channel with T/C
GE 8623-FT-IS Intrinsically Safe Field terminal for 8220-DI-IS
GE 8608-FT-NI Field terminal, 8-channel, non-incendive
GE 8709-CA-08 I/O Carrier, 8 module with earth bar
GE 8717-CA-PS Carrier for 8910-PS-DC