Changes to Configuration in 800xA for Symphony Plus Harmony
The following configuration related changes have been made to 800xA for Symphony Plus Harmony in the 6.0 release:
• The SQL Server based ConfigServer Database that contained 800xA for
Harmony Configuration data has been eliminated in the 6.0 release. The tag
configuration data is now stored in the Aspect Directory.
• The Harmony Synchronizer Aspect, Tag Importer Exporter, and Import Export
Configuration utility have been eliminated. A new Harmony Uploader Aspect
has been added to allow Harmony tag configuration data to be imported to and
exported from the Aspect Directory.
• A new TagConfig Aspect that supports Aspect Directory based tag
configuration has been added. The new TagConfig Aspect also provides
support for 800xA Engineering Environments and Versioning.
• The System Definition object type located under the Harmony OPC Server
Network object has been eliminated. It has been replaced with a new INFI 90
System Definition object in the Library Structure and a new ServerConfig
aspect on the Harmony OPC Server Network object.
• Remote Motor Control Block (RMCB) Text configuration has been removed
from the Harmony Server TagConfig Aspect. RMCB Text configuration is now
provided by a new NLS Text Set on the new INFI 90 System Definition object
in the Library Structure.
• The Harmony Bulk Configuration Manager has been eliminated. The 800xA
Bulk Data Manager can now be used to make bulk changes to 800xA for
Symphony Plus Harmony TagConfig Aspects.
• The 800xA for Harmony Backup/Restore utility has been eliminated. 800xA
for Symphony Plus Harmony tag configuration data can now be backed up and
restored through the standard 800xA Aspect Directory backup/restore.
• The Harmony Server Monitor object and TagMonitor Aspects are no longer
needed and have been eliminated.
Features and benefits
Termination for up to eight (8) analog I/O process signals within a horizontal row.
All SD I/O modules & bases of all types (Singular or Redundant) AND (Compact or Full-size), are
100% fully compatible with each other. Thus, Singular & Redundant, Compact or Full-size I/O
modules can be mounted within a single, common HN800 I/O bus.
Optional mechanical keying can be implemented to prevent insertion of the wrong I/O module type.
Latching device on the base locks the base into position on DIN-Rail.
Industry standard 35-mm DIN rail, Horizontal row mounting.
processor load
• Optical communication
• Industrial grade hardware with no moving parts
• Long life cycle, easy upgrading
• Robust reliance file system, insusceptible post power loss
07EA90-SI ABB modules are used to convert analog signals to digital signals and transmit them to the control system for monitoring and controlling industrial processes.
These accuracy settings are only used when negotiating for time mastership with
other nodes in the underlying Harmony control network.
Master Update Period
Master update period is the frequency that Harmony Server synchronizes time with
the underlying Harmony control network. This property is used only when Time
Synchronization is enabled. The permissible values are 120 to 3540 seconds.
Message Wait Period
Message wait period is the Period that Harmony Server waits before attempting to
assume time mastership on the control network. This property is used only when
Time Synchronization is enabled. The permissible values are between 180 and 3660
seconds. Additionally, the configured value must greater than the Master Update Period.
Sending Global Alarm Acknowledgement Messages to the Loop
Enable Tag Acknowledgment Broadcast
To broadcast an alarm acknowledgement for a specific Harmony tag:
– Select the Tag Acknowledgment Broadcast Enable check box on the Harmony Tab of the tag. Selecting the
checkbox enables the connectivity server to broadcast the alarm acknowledgement for this tag on the communication highway.
Enable Acknowledgment Transmission
Configure the module status tag for each node to which the connectivity server transmits the alarm acknowledgment messages.
For each module status tag, on the Module tab, select the Enable Alarm Acknowledgment
Transmission check box to have the connectivity server transmit any recently acknowledged alarms.
Broadcasts will only be sent to a node when the corresponding module status tag is configured and has alarm acknowledgment transmission enabled.
Receiving Global Alarm Acknowledgement from the Loop
Configure the Harmony Server tag to enable receiving global alarm acknowledgment messages from other nodes on the loop.
On the Harmony tab, select the Global Alarm Acknowledgement check box to
enable the connectivity server to process the Global Alarm Acknowledgement messages received through the INFI-NET loop.
The connectivity server applies the alarm acknowledgement to the harmony tag that has the same Harmony address as the broadcast tag.
You may need the following additional products:
ABB SPK800-PBAT-03 HN800 to PBA to HN800 Cable 3.0 M
ABB VBS01-EPDA Vert. Base Single Ext. Pwr Inputs
ABB VBS01-FPH Vert. Base Single Field Pwr Hot
ABB VBS01-FPHA Vert. Base Single Field Pwr Hot
ABB VBS01-FPN Vert. Base Single Field Pwr Neutral
ABB VBS01-FPNA Vert. Base Single Field Pwr Neutral
ABB VBX01B HN800 Bus Extender Vertical Bottom
ABB VBX01BA HN800 Bus Extender Vertical Bottom
ABB VBX01K02 HN800 Bus Extender Kit Vertical
ABB VBX01K02A HN800 Bus Extender Kit Vertical
ABB SPK800-PBAT-04 HN800 to PBA to HN800 Cable 4.0 M
ABB SPK800-PBAT-0A HN800 to PBA to HN800 Cable 0.5 M
ABB SPRIORBX01K01 HN800 Remote I/O Kit Non-Redundant
ABB SPRIORBX01K02 HN800 Remote I/O Kit Redundant
ABB TER800 HN800 or CW800 Bus Terminator
ABB TER800A HN800 or CW800 Bus Terminator
ABB TER810 HN800 or CW800 Bus Terminator with cover
ABB TER810A HN800 or CW800 Bus Terminator with cover
ABB VBS01-CJC Vert. Base Single Cold Junction Comp.
ABB VBS01-CJCA Vert. Base Single Cold Junction Comp.
ABB VBS01-EPD Vert. Base Single Ext. Pwr Inputs
User name | Member Level | Quantity | Specification | Purchase Date |
---|
wechat/whatsapp:
+86-181-4410-0983
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved