07KT51 Basic Unit
Manufacturers
ABB
Model(s)
ABB Advant Controller 31. ABB Advant OCS
Additional Information
07 KT 51. eight 24 VDC inputs, six transistor outputs
Estimated Shipping Size
Dimensions: 4.0" x 4.0" x 5.0"
(10.2 cm x 10.2 cm x 12.7 cm)
Weight: 0 lbs 12.9 oz (0.4kg )
Features and benefits
Termination for up to eight (8) analog I/O process signals within a horizontal row.
All SD I/O modules & bases of all types (Singular or Redundant) AND (Compact or Full-size), are
100% fully compatible with each other. Thus, Singular & Redundant, Compact or Full-size I/O
modules can be mounted within a single, common HN800 I/O bus.
Optional mechanical keying can be implemented to prevent insertion of the wrong I/O module
type.
Latching device on the base locks the base into position on DIN-Rail.
Industry standard 35-mm DIN rail, Horizontal row mounting.
Time Synchronization
Enable Time Synchronization
Determines whether or not the Server receives and sends the time synchronization
on the network. When enabled, the Server is in time synchronization with the
control network.
Accuracy
Time synchronization accuracy of the Server is valid when the Server is in time
synchronization mode. The options are:
• Low accuracy (lowest accuracy); priority 0.
• Low accuracy battery backed; priority 3.
• High accuracy battery backed; priority 6.
• IIOIS20 node; priority 9.
• IIOIS20 SCSI; priority 10.
• PIMS SCSI; priority 11.
• Satellite clock system (highest accuracy); priority 12.
These accuracy settings are only used when negotiating for time mastership with
other nodes in the underlying Harmony control network.