The I/O configuration portion of the RSLogix 5000® programming software generates the
configuration data for each I/O module in the control system,
whether the module is in a local or remote chassis.
A remote chassis, also known as networked, contains the I/O module but not the module’s owner-controller.
A remote chassis can be connected to the controller via a scheduled connection on the ControlNet network or an EtherNet/IP network.
RSLogix 5000 configuration data is transferred to the controller during the program
download and later transferred to the appropriate I/O modules.
I/O modules in the local chassis, and modules in a remote chassis connected via the EtherNet/IP network,
or unscheduled connections on the ControlNet network, are ready to run as soon as the configuration data has been downloaded.
However, to enable scheduled connections to I/O modules on the ControlNet network,
you must schedule the network by using RSNetWorx for ControlNet software.
Running RSNetWorx™ software transfers configuration data to I/O modules on a
scheduled ControlNet network and establishes a network update time (NUT) for the
ControlNet network that is compliant with the desired communication options specified for each module during configuration.
Anytime a controller references a scheduled connection to I/O modules on a scheduled
ControlNet network, you must run RSNetWorx software to configure the ControlNet network.
See the following general steps when configuring I/O modules.
1. Configure all I/O modules for a given controller by using RSLogix 5000 programming
software and download that information to the controller.
2. If the I/O configuration data references a scheduled connection to a module in a
remote chassis that is connected via the ControlNet network,
run RSNetWorx for ControlNet software to schedule the network.
3. After running RSNetWorx software, perform an online save of the RSLogix 5000 project
so the configuration information that RSNetWorx software sends to the controller is saved.
RTD Error
Module error on the 1756-IR6I module is defined in ohms and is calculated across
the entire input range that is selected, not the available range of a sensor used with the module.
For example, if the 1…487 input range is used, the module error is calculated across 507 (actual range = 0.86…507.86 ).
The error in ohms translates to temperature, but that translation varies because the
relationship is non-linear. The most effective way to check a 1756-IR6I module
error is to calculate the error in ohms and use that value in a linearization table to check the temperatureerror.
If the module is calibrated at operating temperature and the operating temperature remains relatively stable,
calibration accuracy is better than 0.1% of the full range for the first year after calibration.
This 0.1% value is a worst case value. In other words, with the 1…487input range that is selected,
the worst case module error is 0.507.
Finally, you must check an RTD linearization table to determine the temperature error
to which an error of 0.507translates. For example, if the 1756-IR6I has a 0.1% (or 0.507 )
error and is operating at 0 °C (32 °F), the temperature error is -1.25…1.2 °C (-2.25…2.16 °F)
when the Platinum 385 sensor type is used. However, this same ohms error,
when calculated in an operating temperature of 200 °C (392 °F),
translates to a temperature error of -1.4 °C…1.4 °C (-2.52…2.52 °F).
You may also need the following related products:
A-B 1756-M03SE Module Rockwell Servo Control |
A-B 1756-M08SE Module Rockwell Servo Control |
A-B 1756-M08SEG Module Rockwell Servo Control |
A-B 1756-M16SE Module Rockwell 1756 16 Axis Servo Control |
A-B 1756-OA16 module Rockwell ControlLogix 16 digital output |
A-B 1756-OA16I module Rockwell ControlLogix 16 digital output |
A-B 1756-OA8 module Rockwell ControlLogix 8 digital output |
A-B 1756-OA8D module Rockwell ControlLogix 8 digital output |
A-B 1756-OA8E module Rockwell ControlLogix 8 digital output |
A-B 1756-OB16D module Rockwell ControlLogix 16 digital output |
A-B 1756-OB16E module Rockwell ControlLogix 16 digital output |
A-B 1756-OB16I module Rockwell ControlLogix 16 digital output |
A-B 1756-OB16IEF module Rockwell ControlLogix 16-point digital quantity |
A-B 1756-OB16IS module Rockwell ControlLogix 16 digital output |
A-B 1756-OB32 module Rockwell ControlLogix 32 digital output |
A-B 1756-OB8 module Rockwell ControlLogix 8 digital output |
A-B 1756-OB8EI module Rockwell ControlLogix 8 digital output |
A-B 1756-OB8I module Rockwell ControlLogix 8 digital output |
A-B 1756-OC8 module Rockwell ControlLogix 8 digital output |
A-B 1756-OF4 module Rockwell ControlLogix 4 analog |
A-B 1756-OF6CI module Rockwell ControlLogix 6 analog |
A-B 1756-OF6VI module Rockwell ControlLogix 6 analog |
A-B 1756-OF8 module Rockwell ControlLogix 8 analog |
A-B 1756-OF8H module Rockwell ControlLogix 8 analog |
User name | Member Level | Quantity | Specification | Purchase Date |
---|
wechat/whatsapp:
+86-181-4410-0983
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved