Products Description
Manufacturer : Triconex
Product No. : 3601E/T
Product type : Digital Output Module
Type : TMR
Output current range : 4-20 mA Input (+6% overrange)
Number of output points : 8
Isolated points : No, commoned return, DC coupled
Resolution : 12 bits
Output Accuracy : <0.25% (in range of 4-20 mA) of FSR (0-21.2 mA), from 32° to 140° F (0° to 60° C)
Over-range protection : +42.5 VDC, continuous
Switch time on leg failure : < 10 ms, typical
Color code : Pea Green
Weight : 4 kg
Dimension : 9 kg
Shipping weight : 5.6 kg
The Triconex Tricon Safety Instrumented System is designed to meet the needs of safety and critical
control applications in oil and gas, power, refining, chemicals, pharmaceutical and biotech industries.
It is based on industry leading TMR technology, is easy to operate and maintain and provides the lowest total cost of ownership.
Models 3502E, 3503E, and 3505E can self-test to detect stuck-On conditions where the circuitry
cannot tell whether a point has gone to the Off state.
Since most safety systems are set up with a deenergize-to-trip capability, the ability to detect Off points is an important feature.
To test for stuck-On inputs, a switch within the input circuitry is closed to allow a zero input (Off) to be read by the optical isolation circuitry.
The last data reading is frozen in the I/O communication processor while the test is running.
EcoStruxure™ Triconex® - Tricon CX
EcoStruxure™ Triconex Safety System – superior protection for people, production and profits
We understand that you need more from your safety instrumented systems than just keeping your operations safe
you need to keep operations running continuously, avoiding any unexpected downtime or interruption that impacts profitability.
EcoStruxure Triconex - Tricon CX is the most powerful safety system from Triconex.
Leveraging the pedigree of the field-proven Tricon, Trident and Tri-GP systems,
Tricon CX is the best possible choice when safety and profitability are critical success factors.
Applications
• Emergency Shutdown (ESD)
• Burner Management Systems (BMS)
• Fire and Gas Systems (F&G)
• High Integrity Pressure Protection systems (HIPPS)
• Turbo Machinery Controls (TMC)
• Control of critical applications
Operating principals
• Fail Safe — De-energize to trip
• Energize to trip
• Safe, available, secure
Communications
• SIL3 Peer to Peer (254 Nodes)
• OPC DA and A&E (embedded server)
• Modbus TCP/IP Master and Slave
• Modbus Serial Master and Slave
• TSAA
• Copper and Fiber Optic
• ISA Secure EDSA Level 1
Summary of Tricon
Components
Chassis
• Main Chassis—houses Main Processors, memory back-up batteries, communication modules and I/O modules.
• Expansion Chassis—for additional I/O modules up to 100 feet (30meters) away from the Main Chassis. In restricted applications,
operation up to 1,000 feet (300 meters) is supported.
• RXM Chassis—for I/O modules up to 7.5 miles (12 kilometers) away from the Main Chassis.
• Mechanical Keying—Each slot in the Tricon is mechanically keyed to correspond with a specific type of module.
This prevents the installation of modules into improper slots.
Power Supply Modules
• Provide logic power to modules in the Main, Expansion or RXM
Chassis. Available in 24 VDC, 115 VAC and 230 VAC versions. The
power rating of each power supply is 175 watts at 140 ° F (60° C).
Main Processors
The Main Processors execute the system diagnostics and the user-written control program.
Communication Modules
• Tricon Communication Modules (TCM) support a number of Triconex protocols and applications and user-written applications
on Ethernet (802.3) networks, including TriStation, Modbus TCP and OPC.
It also supports RS-232 and RS-485 serial communication with Modbus devices, TriStation 1131. and GPS for time synchronization.
• Enhanced Intelligent
Communication Modules (EICM) support RS-232. RS-422 and RS-485 serial communication with Modbus devices and TriStation 1131.
• Network Communication Modules (NCM) support a number of Triconex protocols and applications and
user-written applications on Ethernet (802.3) networks, including TriStation 1131.
• Safety Manager Modules (SMM) act as an interface between a Tricon controller and a Honeywell Universal Control Network (UCN),
one of three principal networks of the TDC-3000 DCS.
• Hiway Interface Modules (HIM) act as an interface between a Tricon controller and a
Honeywell TDC-3000 Hiway Gateway and Local Control Network (LCN).
• Advanced Communication Modules (ACM) allow a Tricon controller to interface with
a Foxboro Industria Automation (I/A) Series DCS and TriStation 1131.
Related Items we have in stock
Triconex Model 3351 Analog Input Module
Triconex Model 2351Analog lnput Baseplate
Triconex Model 2352 Analog input External Termination Panel Baseplate
Triconex Model 2381 Pulse Input Baseplate
Triconex Solid-State Relay Output Module
Triconex Model 3451 Solid-State Relay Output Module
Triconex Model 2451 Solid-State Relay Output Baseplate
Triconex LO Extender Modules
Triconex Model 2281 LOExtender Module Kit
Triconex Model 2291 lO Extender Module Kit
Triconex Model 2292 VO Extender Module Kit
Triconex Model 9764-310 RTD/TCIAl Termination Panel
Triconex Analog Output Modules
Triconex Model 3481 Analog Output Module
Triconex Model 3482 High-Current Analog Output Module
Triconex Model 2481 Analog Output Baseplate
Triconex Digital lnput Module
Triconex Model 3301 Digital Input Module
Triconex Model 2301 Digital Input Baseplate
Triconex Digital Output Module
Triconex Model 3401 Digital Output Module
Triconex Model 2401 Digital Output Baseplate
Triconex Model 2402 Digital Output Baseplate
Triconex Pulse Input Module
Triconex Model 3381 Pulse Input Module
Triconex Model 3381 Pulse Input Module Specifications
User name | Member Level | Quantity | Specification | Purchase Date |
---|
wechat/whatsapp:
+86-181-4410-0983
Email: kongjiangauto@163.com