Specifications
Power Bases
• Single-phase, 1 controlled leg
Load Amp Range
• 12A, 24A and 48A options (see derating curves)
SCR and Amperage Rating
• SCCR rating 100.000A up to 480VAC with coordinated fusing
• SCCR rating 10.000A up to 240VAC with recommended
circuit breaker
• Power dissipation: Approximately 1 to 1.2 watts per amp
• Leakage current: 1mA at 25°C
Line and Load Voltage Range
• 100 to 480V
Voltage Frequency
• Automatically compensates for 47 to 63Hz
Controller Operating Supply Voltage
• 24VDC, 6W 6VA per ASPYRE AT unit
• Maximum 10 units powered via terminal screw and
backplane connector
• Use split-rail configuration when more units are required
Voltage and Current Measurement Accuracy
• ±2% of range
Control Modes
• Voltage, voltage squared, current, current squared, power
Output Control Firing Types
• Fixed time-base zero crossing
• Variable time-base zero crossing (burst firing)
• Phase angle
Digital Inputs and Outputs
• Independently user-configurable as input or switched DC
output
• Update rate: 10Hz
• Input type: User-selectable, dc voltage or dry contact
• Input logic: On ≥ 4VDC, off ≤ 1VDC, 30VDC max
• Output voltage: 24V (based on the supply voltage)
• Output: 100mADC max. per channel
Analog Input
• Voltage: 0-10VDC, 15kΩ impedance
• Current: 4 to 20mA, 0 to 20mADC, 100Ω impedance
Analog Output
• 0 to 20mADC ±120μA or 4 to 20mADC into 500Ω max. load
with 30μA nominal resolution
• 0 to 10VDC ±60mV into a 500Ω min. load with 15mV
nominal resolution
Electromechanical Relay Output
• Form C, 5A resistive load
• 100.000 cycles at 24VDC, 120/240 VAC
• 125VA pilot duty 120/240VAC
• 25VA 24VAC/DC