Specifications
Universal Analog Inputs 1 (2 and 3 Optional)
• Updates rates, IN1 = 20Hz, IN2 and IN3 = 10HZ
Thermocouple
• Type J, K, T, N, E, C (W5), D (W3), PTII, R, S, B
• Input impedance 20MΩ
RTD
• 2- or 3-wire platinum, 100. 500 or 1000Ω
• JIS or DIN curves, 1.0 or 0.1 indication
Process
• Input resolution ≈50.000 bits at full scale
• Range selectable: 0-10VDC, 0-5VDC, 1-5VDC,
0-50mV, 0-20mA, 4-20mA
• Voltage input impedance 20KΩ
• Current input impedance 100Ω
Digital Inputs (4)
• Update rate = 10Hz
• Contact or dc voltage (36VDC max.)
• 10KΩ input impedance
Control Outputs (1A, 1B, 2A, 2B)
• Update rate = 20Hz
Open Collector/Switched dc
• Internal load switching (nominal):
Switched dc, 22 to 28VDC, limited @ 30mA
• External load switching (max.):
Open collector 42VDC @ 0.5A
Solid State Relay
• Zero switched, optically coupled, 0.5A @ 24VAC min.,
253VAC max.
Process Outputs (Optional Retransmit)
• Update rate = 1Hz
• User selectable 0-10VDC, 0-5VDC, 1-5VDC @
1KΩ min., 0-20mA, 4-20mA @ 800Ω max.
• Resolution:
dc ranges = 2.5mV nominal
mA ranges = 5μA nominal
• Calibration accuracy:
dc ranges = ±15mV
mA ranges = ±30μA
• Temperature stability 100ppm/°C
Alarm Outputs
• Output update rate 1Hz
• Electromechanical relay, Form C, 2A @ 30VDC or
240VAC max.
Digital Outputs (8)
• Update rate = 10Hz
• Open collector output
• Off = 42VDC max. @ 10μA
• On = 0.2VDC max. @ 50mA sink
• Internal supply: 5VDC, @ 80mA
Communications
EIA-232 and EIA-485 serial communications
with Modbus® RTU protocol
Safety and Agency Approvals
• UL®/C-UL® 916 listed, File #E185611
Process Control Equipment
• CE
• EN 61010-1
• EN 61326
• IP65 and NEMA 4X
Terminals
• Touch-safe, removable terminal blocks, accepts
12 to 22 gauge wire
Power
• 100-240VAC, -15%, +10%; 50/60Hz, ±5%
• 24-28VAC/VDC, -15%, +10% (order option)
• 39VA max. power consumption
• Data retention upon power failure via nonvolatile
memory (7 years for battery backed RAM)
• Sensor input isolation from input to input to output to
communication circuitry is 500VAC
Operating Environment
• 32 to 130°F (0 to 55°C)
• 0 to 90% RH, non-condensing
• Storage temperature: -40 to 158°F (-40 to 70°C)
Accuracy
• Calibration accuracy and sensor conformity:
±0.1% of span ±1°C @ 77°F ±5°F (25°C ±3°C)
ambient and rated line voltage ±10% with the following
exceptions:
Type T: 0.12% of span for -328 to -58°F (-200 to -50°C)
Types R and S: 0.15% of span for 32 to 212°F (0 to 100°C)
Type B: 0.24% of span for 1598 to 3092°F (870 to 1700°C)
• Accuracy span: Less than or equal to operating
ranges, 1000°F (540°C) min.
• Temperature stability: ±0.1°F/°F (±0.1°C/°C) rise in
ambient for thermocouples
±0.05°F/°F (±0.05°C/°C) rise in ambient for RTD
sensors
Displays
• Process: 5 digit, 7 segment LED, red
• Control interface display: 4-row, 20-character high
definition LCD green
wechat/whatsapp:
+86-181-4410-0983
Email: kongjiangauto@163.com
Copyright © 2009 - 2024 Cld , All Rights Reserved K-JIANG All rights reserved